TECHNICAL SPECIFICATIONS
Supply Voltage:
115 - 220 VAC, 50 - 60 Hz
Current Draw:
1 Amp. Max.
Fuse (1/4 * 1-1/4):
Fast Blow 1 Amp.
Cable requirement:
LCD Alarm to Remote Sensor:
Important:
Cable:
Belden # 8451 or equivalent. #22 gauge shielded, twisted pair. (For multiple
sensors a multi-conductor twisted pair, shielded cable should be used).
Distance:
Maximum 100 ft [30.5 m]
Signal:
30
VDC
- 1.0
Amps.
60
VDC
- 0.3
Amps.
125 VAC
-
0.5 Amps.
LCD Alarm to Master:
Distance:
Maximum 10,000 ft [3,000 m]
Cable:
Minimum #22 gauge wire
Signal:
5
VDC
- 5.0
Amps.
LCD Generic Alarm:
Output: Dry Contacts NC, open on Alarm.
Rating:
30
VDC
- 1.0
Amps.
60
VDC
- 0.3
Amps.
125 VAC
-
0.5 Amps.