Wiring Schematic Heater Units

The Heaters normally switch on when the temperature drops below 24°C or 75°F. If the temperature exceeds 65-75°C

or 160-175°F, the Heater reset switch will trip and the Heaters will automatically switch off. To reset the Heaters, remove

the Heater covers and press the red button on the reset switch to activate. When the Heaters are in use or switched on,

it will draw up to 3 amps of current. The Heater Cartridge is 200 watts (each side). Normally both sides do not switch on

together, it depends on the flow of gas or climatic conditions.

Inlet Pressure

Block

Power Supply

Reset Switch

Heater Cartridge

Wires

Reset Switch

Inlet Pressure

Block

Heater Cartridge

(Inside Inlet Pressure Block)

Heater Cartridge

(Inside Inlet Pressure Block)