Dynalco SWTD-1000 Speed Switch/Transmitter User Manual

Page 18

Advertising
background image

Operating Instructions SWTD-1000

DYNALCO

16

//

8.5.5 Relay Parameter and Selection of Parameter Set

(Configuration

Æ Relay control)

Parameter set A / B selection

As standard parameter set B may be activated via the binary input <Binary input B1>.
If parameter set B is to be deactivated, this setting should be none (always control A)

Delay time when switching A <- B

This value determines the delay from switching the binary input to the switching from parameter set B to
parameter set A.

Relay assignment with control A

Defines the relay behavior in parameter set A.

Relay assignment with control B

Defines the relay behavior in parameter set B.

Relay

Defines the source information for relay switching.

Status register

Relay dependency

• Alarm

(Common) Alarm

(8.5.1 System Parameters (Configuration

Æ System))

• Sensormonitor Sensor status

(8.5.2 Sensor Parameter (Configuration

Æ Sensor))

• Limit

1/2

Selection of Limit 1/2

(8.5.4 Limit (Configuration

Æ Limit))

• Window

ExOR combination of both limits

• On

The relay is on

• Off

The relay is always off

Acknowledge

Acknowledge establishes if and under what conditions the relay status is held. A relay that is held no
longer reacts to the assigned signal and can only be reset via the binary input.