Figure 2: Possible characteristic measuring value curves
5.1.3.1 Example numerical Teach-in:
1) The measuring range shall be defined from 50mm (A) to 180mm (B) -> (curve 2).
Point A absolute in tenth of mm:
500
01F4 hex (= Measuring range limit A)
Point B absolute in tenth of mm:
1800
0708 hex (= Measuring range limit B)
Parameter to be written:
Measuring range work:
01F40708 hex
2) The output signal shall be inverted; measuring range is from 60mm (B) to 120mm (A) -> (curve 3).
Point A absolute in tenth of mm:
1200
04B0 hex (= Measuring range limit A)
Point B absolute in tenth of mm:
600
0258 hex (= Measuring range limit B)
Parameter to be written:
Measuring range work:
04B00258 hex