PROBLEM CAUSE

SOLUTION

A. Assembly discharges from

Fouled first check

Disassemble and clean No. 1 check valve

differential relief valve during

Fluctuating inlet pressure

Control supply line water pressure

no flow condition.

Outlet pressure higher than inlet pressure

Disassemble, clean #2 check valve &

& leak in No. 2 check valve

identify cause of back pressure.

Leak through diaphragm or around

Service relief valve (page 4)

flange bolt holes of relief valve

Pressure relief valve does not close

See problem D

B. Assembly discharges from

No. 1 check valve wedged open

Disassemble and clean No. 1 check valve

differential relief valve during

O-ring displaced from groove in 1st check

Disassemble and replace

a flow conditions.

Pressure relief valve does not close

See problem D

Fluctuating line pressure

C. Differential pressure relief valve

Differential pressure across No. 1 check

Repair shutoff valves

does not open during test

valve stays above 2psi due to leaking

outlet gate valve

Weak or broken relief valve spring

Disassemble and replace relief valve spring

Shutoff seat tube bound in body

Disassemble and repair

Plugged hydraulic hose

Disassemble and repair

D. Pressure relief valve does

Debris on sealing surface

Remove relief valve and clean

not close

Plugged hydraulic hose

Disassemble and clean

Damaged seat or rubber shutoff disc

Remove relief valve assembly and replace

Ruptured diaphragm

Disassemble and replace diaphragm

Wrinkled or improperly installed diaphragm

Disassemble and properly position diaphragm

Troubleshooting Guide

Problem Identification Procedures

When using differential pressure gauge:

A. Check differential across No. 1 check valve

READING

PROBLEM

2 to 3 psid

Leak in No. 1 or No. 2

check valve

4 to 7 psid and steady Malfunctioning pressure

relief valve

2 to 7 psid fluctuating

Inlet pressure fluctuation

Without using differential pressure gauge:

A. Close gate valve No. 2

RESULT

PROBLEM

If discharge stops

Leak in No. 2 check valve

If discharge does

Go to B

not stop

B. Open No. 4 testcock to produce a flow greater than

differential relief valve discharge

RESULT

PROBLEM

If discharge stops

Leak in No. 1 check valve

If discharge does

Malfunctioning pressure

not stop

relief valve