Installation guidelines, Indoor installation, Outdoor, above ground installation – Ames Fire & Waterworks 400B Bronze Reduced Pressure Zone Assemblies User Manual

Page 2: Parallel installation

Advertising
background image

2

Installation Guidelines

Indoor Installation

For indoor installations, make sure the Series 400B is easily

accessible to facilitate testing and servicing. Do not install in

concealed locations. If the location of the Series 400B is parallel

and close to the wall, make sure the test cocks are easily

accessible, and the drain line can adequately drain if required. An

air gap and drain line (see literature ES-A-AG/EL/TC) are piped

from the relief valve connection as shown, allowing evidence of

discharge to be clearly visible and preventing the occurrence of

water damage.

Outdoor, Above Ground Installation

For outdoor installations, it is recommended that you install the

Series 400B-A where there are no freezing conditions and above

ground whenever possible.

You must install the Series 400B in an accessible location to

facilitate testing and servicing. The installation must also allow for

adequate drainage from the air gap and the discharge line

if needed.

WARNING

!

1. Do not allow the drain line to empty directly into a drainage

ditch, sewer system, or sump.

2. Do not install the Series 400B in any location where any part

of the unit could become submerged in standing water.

Air Gap

Strainer

Meter

12" (300mm) Minimum

(refer to local codes)

Ames

400B S

Ames

400B-A

Ames Series 400B Reduced Pressure Zone Assemblies

A. Shutoff Valves: If you remove the shutoff valves from the Series

400B, reassemble the shutoff valve with the test cock mounted

on the inlet side of the unit.

B. Always install the Series 400B in an accessible location to

facilitate testing and servicing (See page 2). Check the state and

local codes to ensure that you install the backflow preventer in

compliance with those codes, such as the proper height above

the ground.

C. It is recommended that you install a strainer ahead of the Series

400B assemblies to protect the internal components from un-

necessary fouling.

CAUTION

!

Do not install a Series 400B with a strainer in rarely used water

lines, such as a fire sprinkler system which is only used during

emergencies.
Start Up: Close the downstream shutoff. Open the upstream

slowly and fill the valve. When the valve is filled, open the

downstream shutoff slowly, and fill the water supply system. This

is necessary to avoid water hammer and/or shock damage.
D. Vent the air gap and drain line from the relief valve in accor-

dance with code requirements. Terminate discharge approxi-

mately 12" (300mm) above the ground or through an air gap

piped to a floor drain.

Min. 12" (300mm)

Parallel Installation

For parallel installations, you can install two or more small sized

Series 400B’s (when approved) to serve a large supply pipe

main. You can use this type of installation in an application where

increased capacity beyond that provided by a single valve is

required. Additionally, this type of installation permits testing and/

or servicing of a single valve without shutting down the complete

line.

The number of Series 400B units installed in parallel should be

determined by the engineer’s judgement, based on the operating

conditions of a specific application.

NOTICE

The total capacity of all the units installed in the application

should equal or exceed that required by the system.

Ames

400B

Advertising