Status indicator sticker, Adjustment switches – Carrier 16DF013-050 User Manual

Page 15

Advertising
background image

Status Indicator Sticker —

The sticker shown in

Fig. 11 is located on the front of the control panel. It iden-
tifies the basic codes for machine operating status and safety
shutdown, as displayed by the 3-character indicator on the
front of the control panel.
NOTE: See Digital Temperature Display, page 16, and Ad-
justment Switches, below, for switch selections that display
temperatures being measured by the machine sensors as well
as the machine cumulative run time.

Adjustment Switches —

These are located on the cir-

cuit board on the inside panel door.

TOGGLE SWITCHES (Fig. 12) — These are summarized
in Table 6 and discussed in greater detail in various sections
throughout this manual.

Table 6 — Control Panel Toggle Switches

SYMBOL

TOGGLE SWITCH

DESCRIPTION

TS1

On-Off

Direct Current Power Supply

TS2

Auto.-Manual

Dilution Valve

TS3

Cool-Heat

Select Cool/Heat

TS4

Open-Close

Capacity Control Valve

TS5

Auto.-Manual

Capacity Control Valve

TS6

Remote-Local

Operation

NOTES:
1. Time display selection shows the cumulative machine operating time in hours

on the panel door operating status indicator. With the capacity control valve
selection in the AUTO. position, momentarily depressing the switch to OPEN
displays the first 3 digits of the time, and depressing the switch to CLOSE
displays the last 2 digits and decimal. Example:
OPEN position indicates = 012
CLOSE position indicates = 345
Cumulative run time = 01234.5 hours

2. With capacity control valve selection in the MANUAL position, momentarily

depressing the switch to OPEN or CLOSE will move the burner fuel control
valve and air damper proportionally open or closed.

Fig. 11 — Control Panel Status Indicator Sticker

Fig. 12 — Control Panel Toggle Switches

15

Advertising