Vii venting, Viii steam boiler piping and trim installation, Ix water boiler piping – Crown Boiler 32-380ECS User Manual

Page 4: X gas piping

Advertising
background image

VII Venting

Refer to installation manual. Vent sizing for the 32-380ECS should always be done in accordance with the National Fuel

Gas Code.

A vent damper can be installed on any 32-380ECS or 32-475ECS equipped with a 24 volt control system except for those

with tankless heaters. If a vent damper is installed, the following components are required:

Effikal Model GVD-12 Vent Damper: Crown PN 96-038

Damper Harness (Steam Boilers): Crown PN 9601300

Damper Harness (Water Boilers): Crown PN 9601550

To install the damper:

1) Open vent damper carton and remove installation instructions. Read the instructions thoroughly before proceeding. Verify

that vent damper is same size as draft diverter outlet (12”). Unpack vent damper carefully. Do not force closed damper

blade. Forcing vent damper closed may result in damaged gear train.

2) Vent damper is factory shipped having approximately ¾” diameter hole in the vent damper blade, which must be left

open even though this boiler is equipped with an intermittent ignition system.

3) Mount the vent damper on the flue collar without modification to either and secure with sheet metal screws. Make

sure screws do not interfere with damper blade operation. Vent damper blade position indicator must be visible to users.

Maintain at least 6 inches between the vent damper device and combustible construction. Also make sure that there is

adequate access to the vent damper for servicing. Figures D and F in the Wiring section show typical damper orientation.

4) Install vent connector pipe and vent fittings from vent damper outlet to chimney or gas vent. Secure with sheet metal

screws and support as required.

5) See the Wiring section of this supplement for instructions on making damper electrical connections.

VIII Steam Boiler Piping and Trim Installation

Refer to installation manual. The #67 low water cut-off (LWCO) cannot be used as the primary (operating) LWCO on the

380ECS or 475ECS. Instead, a Hydrolevel CG400 is installed in tapping “G” (Figure 22). A #67 LWCO can be used as

a redundant LWCO (with or without manual reset) in tappings “E” along with the level glass. The CG400 supplied with

this boiler uses the same flangeless probe, and is mounted on the boiler in the same manner, as the CG450 described in the

installation manual at the top of page 28. Install the 32-380ECS near boiler piping in accordance with that shown for the

32-475 in Figure 27a in the installation manual.

IX Water Boiler Piping

Refer to installation manual. Boilers covered by this supplement which are not equipped with a tankless heater are supplied

with a Honeywell L8148E limit control installed in Tapping “C” (Figure 29) using the 1/2” well and 1/2 x 1-1/2” bushing

supplied. Boilers equipped with a tankless heater are supplied with a Honeywell L8124E, which is installed using a 3/4”

well in the tankless heater. The L4006A shown in the installation manual is not used.

X Gas Piping -

Refer to installation manual

WARNING

Install the vent damper directly on top of the boiler so that it is servicing only the boiler.