When you have determined that there are no leaks in the gas
piping system you may purge the system of air. Disconnect the
pilot supply tubing from the right side of the valve. See Figure
12.

Turn the knob on the gas valve to the pilot position. Press the
knob down and hold until you smell gas at the pilot supply
opening. Release the knob and turn it to the off position.
Reconnect the pilot supply tubing and check for leaks with soap
and water or liquid detergent.

WARNING

When purging gas piping, the area around the floor furnace must
be well ventilated to allow any gas to dissipate. Liquid Petroleum
(L.P.) Gas is heavier than air and may puddle in low places under
the floor. Check thoroughly to determine that no gas is present
before lighting the floor furnace. Failure to do so could result in
property damage, bodily injury or death.

THERMOSTAT INSTALLATION

Follow the instructions included with the thermostat. Locate the thermostat approximately five feet above the floor. Always
mount the thermostat on an inside wall where it won’t be affected by heat or cold sources such as direct sunlight, televisions,
fireplaces, hidden hot or cold water pipe, drafts, etc. The thermostat must never be installed in an adjoining room where a door
can be closed between the thermostat and floor furnace. This floor furnace is equipped with a self-generating control system.
Never connect to a 24-volt transformer or to the household electric system. Do not use more thermostat wire than is included
with the floor furnace.

WIRE AS INDICATED: (See Figure 13)

Step 1. Connect black limit switch wire to black thermostat wire using wire nut. (Nut not furnished).
Step 2. Connect white thermostat wire to terminal on gas valve marked “TH PP”.
Step 3. Connect white limit switch wire to terminal on gas valve marked “TH”.
Step 4. Connect the thermostat wires to the thermostat following the instructions provided by the thermostat manufacturer.

THERMOSTAT

LIMIT SWITCH WIRES

WIRE NUT

POWERPILE
GENERATOR

TERMINAL BLOCK
ON GAS VALVE

Thermo-
stat

Limit
Switches

Red

Black

White

White

Powerpile

Generator

TH

TP

TH

TP

Terminal Block

FIGURE 13

Page 10

CHECKING THE GAS PIPING - CONTINUED

Limit Switch Wires

Pilot Supply
Tubing

Pressure Tap

Pilot
Adjustment

FIGURE 12