Clearance Requirements

Minimum Clearances to

Combustible Materials

Measure side clearances as shown in Figures 2
through 5 from the outer edge of the cast iron stove top.
Measure rear clearances from the outermost surface of
the sheet metal rear skirt.
The Dutchwest heater is approved for installation into
an alcove constructed of combustible materials to the
dimensions and clearances shown in Figure 5.
The same clearances apply in a standard parallel instal-
lation.

Hearth Requirements

The Dutchwest Heater must be installed on rigid floor-
ing. When the heater is installed directly on any com-
bustible surface other than wood flooring, a metal or
wood panel extending the full width and depth of the
unit must be used as the hearth. There are no other
hearth requirements.

WARNING:

• Always maintain required clearances

(air spaces) to nearby combustibles

to prevent fire hazard. Do not fill air

spaces with insulation. All venting compo-

nents must maintain a 1” (25 mm) clearance to

combustible materials. Maintain a 6” (152 mm)

clearance when using single wall pipe.

• The gas appliance and vent system must be

vented directly to the outside of the building

and never be attached to a chimney serving a

separate solid fuel or gas-burning appliance.

• Refer to the manufacturer’s instructions in-

cluded with the venting system for complete

installation procedures.

Ceiling Clearances

ST774

Fig. 4 Minimum ceiling clearance; minimum alcove height.

72"

(1829mm)

ST774

Dutchwest

nv

Min. Clg Clrnc

6/03 djt

45"

(1140mm)

Parallel Installation: Minimum Clearance

and Flue Centerline

Stove Clearances

A: 5” (125mm)

B: 4” (102mm)

Pipe Centerlines

C: 16” (406mm)

D: 9¹⁄₄” (235mm)

ST128c

Fig. 2 Parallel installation requirements.

ST128b

Stardance

flue centerline

9/28/00 djt

C

L

C

L

B

D

C

A

Corner Installation: Minimum Clearance and

Flue Centerline

Stove Clearance

A: 4” (102mm)

Pipe Centerline

B: 17” (432mm)

ST129c

Fig. 3 Corner installation requirements.

ST129c
Dutchwest
corner specs
5/15/03 djt

A

A

B

B

Alcove Minimum Dimensions

A: 4” (102mm)

B: 33” (838mm)

C: 5” (125mm)

ST775

Fig. 5 The Dutchwest Natural Vent Stove is approved for

installation into alcoves built of combustible materials.

ST658

SNV

alcove mins.

5/25/01 djt

B

A

A

C