Installation – Craftsman 351.223140 User Manual
Page 5
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
 
ATTACH INLET
Refer to Figure 7.
Inlet needs to be attached to right side of dust collector 
assembly. To attach inlet:
• 
Position inlet over 2'h" hole on right side of dust collector 
assembly.
•
Secure inlet using four 4.2-1.4 x 12mm thread-forming 
screws.
ATTACH HOSE
Refer to Figure 8.
Hose needs to be attached to the inlet using hose clamp.
To attach hose:
•
Slide hose clamp onto one end of hose. Loosen clamp 
screw if required to slide hose clamp onto hose.
•
Position the hose clamp wires on the hose grooves.
•
Slide hose with clamp onto inlet.
•
Tighten hose clamp screw to secure hose with inlet.
•
Slide other hose clamp onto the opposite hose end. This 
end will be connected to the dust producing machine
Ill®
-os:
. Jl,
Hose
^^^^^■ClampJ
■
Figure 8 - Attaching Hose
INSTALLATION
DANGER;
Do not permit fingers to touch terminals of plug
when installing or removing the plug to or from the outlet.
WARNING:
Do not connect to power source until unit is
completely assembled.
POWER SOURCE
•
Motor is designed for operation on the voltage and fre
quency specified on motor nameplate.
•
Normal loads will be handled safely on voltages not more 
than 10% above or below the specified voltage.
•
Running unit on voltages not within range may cause over
heating and motor burnout.
GROUNDING INSTRUCTIONS
Refer to Figure 9.
•
This tool is equipped with a 3-conductor cord.
•
Do not remove or alter grounding prong in any manner. In 
the event of malfunction or breakdown, grounding provides 
path of least resistance for electrical current to reduce risk 
of electrical shock.
•
Plug must be plugged into a matching outlet that is proper
ly installed and grounded in accordance with all local 
codes and ordinances.
•
The conductor with insulation having an outer surface 
which is green is equipment grounding conductor. If repair 
or replacement is necessary, make sure equipment 
grounding conductor is not connected to line terminal.
•
If power cord is worn, cut or damaged in any way, have it
replaced immediately.
Properly Grounded Outlet
Grounding Prong
3-Prong Plug
Figure 9 - 3-Prong Receptacle
CAUTION: Improper connection of the equipment-grounding
conductor can result in a risk of electrical shock.
EXTENSION CORDS
•
The use of any extension cord will cause some drop in the 
voltage and loss of power.
•
Wires of the extension cord must be sufficient in size to 
carry the current and maintain adequate voltage.
•
Use the table below to determine the minimum wire size 
(A.W.G.) extension cord.
•
Use only 3-wire extension cords having 3-prong grounding 
type plugs and 3-pole receptacles which accept the tool 
plug.
•
If extension cord is worn, cut or damaged in any way, have
it replaced immediately.
Extension Cord Length
Wire Size
A.W.G.
Up to 50 ft........................................................................................ 16
Note; Using extension cords over 50 ft. long is not
recommended.