Carrier’s packaged selection program provides quick,
easy selection of Carrier’s water-cooled chillers. The pro-
gram considers specific temperature, fluid and flow
requirements among other factors such as fouling and alti-
tude corrections.

Before selecting a chiller, consider the following points:

Leaving water (fluid) temperature (LWT)
• The LWT must be at least 40 F (4.4 C) or greater.
• If the LWT requirement is greater than 60 F (15.5 C), a

mixing loop is required.

Entering water (fluid) temperature (EWT)
• If the EWT requirement is greater than 70 F (21.1 C), a

mixing loop is required. The EWT should not exceed
70 F (21.1 C) for extended operation. Pulldown can be
accomplished from 95 F (35 C).

Evaporator flow rate or evaporator delta-T:
• The evaporator delta-T (EWT – LWT) must fall between

5 and 20° F (2.8 and 11.1° C) while still meeting the
maximum entering requirements.

• For larger or smaller delta-T applications, a mixing loop

is required.

If the evaporator flow is variable, the rate of

change of flow should not exceed 10% per minute.
The loop volume in circulation must equal or exceed
3 gallons per nominal ton (3.2 L per kW) of cooling for
temperature stability and accuracy in normal air condi-
tioning applications. In process cooling applications,
there should be 6 to 10 gallons per ton (6.5 to 10.8 L
per kW). To achieve this loop volume, it is often neces-
sary to install a tank in the loop. The tank should be baf-
fled to ensure there is no stratification, and that water
(or brine) entering the tank is adequately mixed with liq-
uid in the tank. See Water Loop Volume in the Applica-
tion Data section.

Evaporator pressure drop:
• A high evaporator pressure drop can be expected when

the evaporator delta-T is low. A mixing loop can help to
alleviate this situation.

• The three-pass evaporator option is recommended to

increase performance when the evaporator delta T is
high. This is particularly helpful with brine applications.

Condenser pressure drop:
• A high condenser pressure drop can be expected when

the condenser delta-T is low. A one-pass condenser can
help lower pressure drop.

Series chillers:
• One-pass heat exchangers can help lower pressure

drop when heat exchangers are placed in series.

Water quality, fouling factor:
• Poor water quality can increase the required evaporator

fouling factor.

• Higher than standard fouling factors lead to lower

capacity and higher input kW from a given chiller size
compared to running the same application with better
water quality (and lower fouling factors).

Temperature reset:
• Return water (standard)
• Outside air temperature (standard)
• Space temperature (accessory sensor required)
• 4 to 20 mA (requires an energy management module)
Demand limit:
• 2-step (requires an energy management module)
• 4 to 20 mA (requires an energy management module)
• CCN Loadshed

Performance data

EVAPORATOR AND CONDENSER FLOW RATES

*Maximum condenser fluid temperature shown for standard condensing
option. Heat machine option may have leaving fluid temperatures up to
140 F (60 C).

30XW UNIT

EVAPORATOR

CONDENSER

NOMINAL

Leaving Fluid/Entering Fluid

Minimum Entering

Fluid

Maximum Leaving

Fluid

Evaporator

Condenser

Minimum

Maximum

40 F (4.4 C)/

45 F (7.2 C)

60 F (15.6 C)/

70 F (21.1 C)

65 F (18.3 C)

118 F (47.8 C)*

Minimum

Flow Rate

Maximum

Flow Rate

Minimum

Flow Rate

Maximum

Flow Rate

Nominal

Flow Rate

Nominal

Flow Rate

GPM

L/s

GPM

L/s

GPM

L/s

GPM

L/s

GPM

L/s

GPM

L/s

325

Two pass

411

25.9

1481

93.4

494

31.1

1974

124.5

790

49.8

987

62.3

One pass

790

49.8

3126

197.2

987

62.3

3290

207.6

790

49.8

987

62.3

Three pass

247

15.6

987

62.3

790

49.8

350

Two pass

433

27.3

1557

98.2

519

32.7

2076

131.0

830

52.4

1038

65.5

One pass

830

52.4

3287

207.4

1038

65.5

3460

218.3

830

52.4

1038

65.5

Three pass

260

16.4

1038

65.5

830

52.4

400

Two pass

486

30.7

1751

110.4

584

36.8

2334

147.3

934

58.9

1167

73.6

One pass

934

58.9

3696

233.1

1167

73.6

3890

245.4

934

58.9

1167

73.6

Three pass

292

18.4

1167

73.6

934

58.9

Selection procedure