Series 5500 XTherm

Curtain Wall Assembly and Installation Instructions

Section 13 - Glazing Preparation

1. Install Fl08 setting block into bottom reglet as shown below. Setting blocks are typically located at 1/4 points refer to shop drawings for special locations.

Customer / Installer Note: EFCO setting block are typically 4” in length worth different depths. If the glazing infill is “ NOT BY EFCO” and glazing sizes are larger

than 40 square feet, then the glazing details must be reviewed by the glazing manufacturer for proper setting block size and location.