KMC Controls CME-7002 User Manual

Installation guide, Auxiliary switches

Advertising
background image

CME-7001/7002 Auxiliary Switches

1

Installation Guide

Installation Guide

Auxiliary Switches

CME-7001/7002

Mounting

1

Wiring and Dimensions 2
Maintenance

2

Important Notices 2
Specifications 2

Mounting

These auxiliary switches are designed to start and

stop auxiliary items or to indicate an actuator’s fully

open or closed position. The single or dual switch

models are fully adjustable over the actuator’s 0 to

90° rotation. Switches are independently adjustable

for a trip point anywhere within the angular rotation

of the driving actuator.
They are designed to mount on any KMC MEP-7000

Series Actuator as described here:
1. Insert the “D” shaft, found on the underside of

the switch box, into the “D” hub on top of the

actuator cover.

2. Fasten the switch box to the actuator with 4

screws (provided). This requires punching the

screws through the label on the actuator cover.

3. Depress the gear disengagement button (red) and

rotate the actuator fully counterclockwise (CCW).

4. Loosen the center screw on the switch dial.
5. Turn the switch dial until the arrow on the dial

is pointing at the desired switching point on the

scale.

6. Tighten the center screw on the switch dial to lock

the switching position.

7. Verify the correct switching point by manually

rotating the actuator. The switch dial is

mechanically coupled to the actuator’s gear train

and will follow the actuator’s rotation. The switch

operates each time the arrow on the switch dial

passes “0” or “90” on the scale.

8. See the Wiring and Dimensions section on the

next page.

“D” Shaft

Screws

Advertising
This manual is related to the following products: