Connecting to controllers – KMC Controls XEE-6311 User Manual

Page 3

Advertising
background image


Digital Designer’s Guide

AN0604D Revision B

Tips for connecting 24-volt power

Connecting to controllers

1–17

Connecting to
controllers

KMC Controls recommends supplying power to each controller from a
transformer dedicated to the controller. Illustration 3 is a typical connection of a
KMC XEE–6000 series transformer connected to a KMC controller. The usual
practice is to connect the phase (usually blue) wire of the transformer secondary
to the phase or ~ terminal and the common (usually brown) wire connected to the
– or ground terminal. Other transformers may use a different color scheme.
Unless required by an electrical code requirement, do not ground either lead of
the secondary.

–

–

24 VAC

120 VAC

Connecting several controllers to a single transformer

When more than one controller must be powered from a common transformer,
connect as shown in Illustration 3. In addition, observe the following
requirements:

◆

Connect the phase (~) terminals in parallel with other phase terminals and
the commons (–) in parallel with the other common terminals. See
Illustration 4.

◆

If the secondary must be grounded, ground it at only one location. See

Grounded secondary connections

on page 1-18.

◆

Connect only controllers with the same type of power supply. Controllers
with half-wave power supplies and full-wave power supplies cannot be
powered directly by the same transformer. See

Grounded secondary

connections

on page 1-18.

◆

Choose a transformer with the correct VA rating. See

Calculating transformer

size

on page 1-21.

◆

Choose a wire size that limits the voltage drop to no more than 5%. See

Calculating voltage drop

on page 1-22.

Illustration 3 Connecting to a single controller

Advertising