Load balancing example #1, Load balancing example #2 – Reliance Controls 30216BRK User Manual

Page 6

Advertising
background image

Circuit Breaker Connections: Six (6) 120 Volt Single Pole Circuit Breakers

Generator: 5,500 Running Watts, 6,200 Peak Watts

Transfer Switch Model: 6-Circuits

Side One

Side Two

Appliance

Additional

Appliance

Additional

Toggle

Main Appliance

Running

Start-Up

Toggle

Main Appliance

Running

Start-Up

Switch

Hooked Up

Watts

Watts

Switch

Hooked Up

Watts

Watts

A

Refrigerator

800

2,300

F

Furnace

700

1,400

B

Sump Pump

800

1,300

E

TV, VCR, Computer

600

0

C

Indoor Lighting

300

0

D

Security, Lighting

500

0

Total Running Watts Side
One:

1,900

Total Running Watts Side
Two:

1,800

Total Side One and Side Two Running Watts

3,700

Highest Additional Start-Up Wattage of all of the Appliances (Refrigerator)

2,300

Total Watts of Load

6,000

Peak Wattage Rating of Your Generator

6,200

You're OK!

Page 5

Load Balancing Example #1

Circuit Breaker Connections: Four (4) 120 Volt Single Pole Circuit Breakers and One (1)

240 Volt Double-Pole Circuit Breaker (Toggles C & D Together)

Generator: 5,500 Running Watts, 6,200 Peak Watts

Transfer Switch Model: 6-Circuits

Side One

Side Two

Appliance

Additional

Appliance Additional

Toggle

Main Appliance

Running

Start-Up

Toggle

Main Appliance

Running

Start-Up

Switch

Hooked Up

Watts

Watts

Switch

Hooked Up

Watts

Watts

A

Refrigerator

800

2,300

F

Furnace

700

1,400

B

TV, VCR, Computer

600

0

E

Sump Pump

800

1,300

C

Well Pump

500

1,175

D

Well Pump

500

1,175

Total Running Watts Side
One:

1,900

Total Running Watts Side
Two:

2,000

Total Side One and Side Two Running Watts

3,900

Highest Additional Start-Up Wattage of all of the Appliances (Refrigerator)

2,300

Total Watts of Load

6,200

Peak Wattage Rating of Your Generator

6,200

You're OK Again!



Load Balancing Example #2