42bvc unit corner weights (lb) – Carrier AIRSTREAM 42BHC User Manual

Page 13

Advertising
background image

13

1

3

2

4

4

3

1

2

1

1

2

4

3

3

4

2

RIGHT HAND UNIT

LEFT HAND UNIT

42BVC UNIT CORNER WEIGHTS (lb)

TOTAL WEIGHT UNIT CORRECTION FACTOR (lb)

Corner weights on pages 12 and 13 are for 8-row water filled coils. For a different number of rows, total unit weight
can be determined by the following procedure:
• Identify the number of rows and the size of the unit.
• Determine the total weight of the unit from the Corner Weight tables.
• From the table below, identify the correction factor (for size of unit and number of rows) and subtract this from the

total weight.

UNITS

42BHC,BVC

4 ROWS

5 ROWS

6 ROWS

7 ROWS

Correction Factors (lb)

06

21

16

11

5

08

21

16

11

5

10

28

21

14

7

12

28

21

14

7

16

39

29

20

10

20

46

35

23

12

30

74

55

37

18

40

98

74

49

25

NOTE: Unit weights (shown in pounds) ±10% are based on the 8-row coil and 1 Hp motor.

UNIT

42BVC

CONFIGURATION

RIGHT-HAND UNITS

LEFT-HAND UNITS

TOTAL

WEIGHT

1

2

3

4

1

2

3

4

06

No Heat

52

54

51

43

54

52

43

51

200

With Heat

58

65

61

47

65

58

47

61

231

08

No Heat

53

55

51

43

55

53

43

51

202

With Heat

58

66

62

47

66

58

47

62

233

10

No Heat

63

69

61

50

69

63

50

31

243

With Heat

69

81

72

54

81

69

54

72

277

12

No Heat

64

70

62

51

70

64

51

62

247

With Heat

70

82

73

55

82

70

55

73

281

16

No Heat

74

85

72

58

85

74

58

72

289

With Heat

80

98

84

61

98

80

61

84

323

20

No Heat

90

108

86

68

108

90

68

86

351

With Heat

95

123

99

71

123

95

71

99

387

30

No Heat

110

139

106

81

139

110

81

106

436

With Heat

115

155

120

83

155

115

83

120

473

40

No Heat

131

172

125

94

172

131

94

125

522

With Heat

135

190

140

95

190

135

94

140

559