MODEL 950-1007 AND 950-1032 FAN PROVER KITS

Disconnect power supply to all heating, venting equipment and controls before making wiring connections to prevent electrical
shock and equipment damage.

REPLACEMENT OF OLD STYLE FAN PROVER SWITCHES PREVIOUSLY MOUNTED ON ELECTRICAL BOX (SEE DIAG. A)

1. Disconnect power supply to all heating equipment and remove old Fan Prover switch

from HS-3, 4, 5 electrical box.

2. Mount new Fan Prover switch with the diaphragm in a vertical orientation within 2 feet

of HS-3, 4, 5 electrical box and within 4 feet of the Power Venter for 1/4” aluminum
tubing connection.

3. Attach conduit mounting plate with whip assembly to HS-3, 4, 5 electrical box with 2

provided screws and connect 2 foot whip to new Fan Prover electrical box by using
provided fittings.

4. Connect the 1/4” aluminum tubing from the Fan Proving Switch to the Power Venter

housing using existing supplied fittings. The factory calibrated sensing tube length and
compression fittings are critical for proper operation of the Fan Proving Switch. If it is
necessary to alter the sensing tube length, ONLY trim sensing tube portion that is on
the exterior of the housing. IMPORTANT: DO NOT trim the sensing tube portion that
will be mounted in the interior of the housing because Fan Prover will not sense the
proper pressure. Sensing tube assembly with factory calibrated length must be
used for Fan Prover to work properly!

5. Cut female quick connect leads off of wires that were connected to old Fan Prover and

wire nut these wires to the new leads from 2 foot whip connected to new Fan Prover.
Connect leads in new Prover electrical box. Prover leads are not polarity sensitive so
connection order on switch terminals does not matter.

6. Reestablish power and run heating equipment through a couple of heating cycles to verify proper operation.

REPLACEMENT OF SIMILAR STYLE FAN PROVER SWITCHES WITH THEIR OWN ELECTRICAL BOX (SEE DIAGRAM B)

1. Disconnect power supply to all heating equipment and remove Blue and

Yellow leads from old Fan Prover switch and motor lead connections in
old Fan Prover junction box.

2. Mount new Fan Prover in a vertical orientation in the same location as

old Prover. You can use the old Fan Prover sensing tubing as long
as it is not damaged or kinked. If damaged, replace with new tubing.

3. Connect the 1/4” aluminum tubing from the Fan Proving Switch to the

Power Venter housing using existing supplied fittings. The factory calib-

rated sensing tube length and compression fittings are critical for proper

operation of the Fan Proving Switch. If it is necessary to alter the sens-

ing tube length, ONLY trim sensing tube portion that is on the exterior of

the housing. IMPORTANT: DO NOT trim the sensing tube portion that

will be mounted in the interior of the housing because Fan Prover will

not sense the proper pressure. Sensing tube assembly with factory

calibrated length must be used for Fan Prover to work properly!

4. Connect existing conduit from Venter motor and controls to new Fan

Prover.

5. Reconnect Blue and Yellow leads removed in step 1 to the new Fan

Prover switch. Prover switch leads are not polarity sensitive. Reconnect

motor leads removed in step 1 in new Fan Prover Junction box.

6. Reestablish power and run heating equipment through a couple of

heating cycles to verify proper operation.

Rev. 11/02

Copyright © 2002, Tjernlund Products, Inc. All rights reserved.

P/N 8504113

TJERNLUND PRODUCTS, INC.

1601 Ninth Street • White Bear Lake, MN 55110-6794
PHONE (800) 255-4208 • (651) 426-2993 • FAX (651) 426-9547
Visit our web site • www.tjernlund.com

FAN PROVER

VENTER

5 FT. LENGTH PROVIDED

S ADDITIONAL CONDUIT,

MINIMUM 14 GAGE)

2 FT. MAXIMUM LENGTH UNLESS ADDITIONAL CONDUIT,

J-BOX AND WIRE ARE ADDED (MINIMUM 14 GAGE)

T. MAXIMUM LENGTH

ALUMINUM SENSING TUBE

SIDE OF SENSING TUBE

DO NOT ALTER THIS

HOUSING WALL

SENSING TUBE

ASSEMBLY

SENSING TUBE

COMPRESSION RING

BRASS ELBOW FITTING

COMPRESSION RING

AND WIRE ARE ADDED

DIAGRAM B

FAN PROVER

VENTER

SIDE OF SENSING TUBE

DO NOT ALTER THIS

HOUSING WALL

SENSING TUBE

ASSEMBLY

SENSING TUBE

COMPRESSION RING

BRASS ELBOW FITTING

COMPRESSION RING

MOUNTED VERTICAL

ELECTRICAL

BOX

CONDUIT

MOUNTING

PLATE

DIAGRAM A