6

State Of Charge Sealed or Flooded

Lead Acid

GEL Battery

AGM Battery

100%

12.7+Volts

12.9+Volts

12.8+Volts

75%

12.4 Volts

12.7 Volts

12.6 Volts

50%

12.2 Volts

12.4 Volts

12.3 Volts

25%

12.0 Volts

12.0 Volts

12.0 Volts

10%

11.8 Volts

11.8 Volts

11.8 Volts

Voltage Meas (DC)

V1, V2, V3, V4 = 1-80VDC

Voltage Meas Accuracy

+/- 0.1V

Current Meas (DC)

I1, I2 = 0.1A to 20A

I3, I4 = +/-10A

Current Meas Accuracy

+/- 0.1A

Temperature Meas

T1,T2 = -40C to 125C

Temp Meas Type

T1 = Embedded, T2 = External Sensor (included)

Temp Meas Accuracy

+/- 1 degC

Relays (Normally Closed

Type)

R1, R2, R3, R4 = 10A DC

Relay Control

R1, R2 = Manual or Ping or Time Control

R3, R4 = Manual or Temperature Control

Power Requirements

10-58VDC Wire Terminal or 802.3af Class 0 POE,

3W Typ

Accessibility

Via Web Browser and SNMP

Data-Logger

FIFO, Max 1300 data sets, Program log interval

Connections

Removable Wire Terminal

Wire Size

12AWG Max

Mounting

DIN Rail

Operating Temperature

-40C to +75C (-40F to 167F)

Humidity (RH)

0% - 90%

Dimensions (LxWxH)

125 x 102 x 46mm (4.9” x 4” x 1.8”)

Weight

410g (14.5 oz)

5. Operating Power: The TPDIN-Monitor-WEB has extremely low op-

erating power, typically less than 3W. The relays are normally closed

type so in typical operation they don’t take any power until they are en-

ergized. If the relays are turned on to hold them open, the power usage

will increase.

6. SNMP: The TPDIN-Monitor-WEB can be controlled via SNMP for

automated operation. Setup the SNMP on the SNMP page in the web

interface. The unit will respond to SNMP queries to gather data and

control relays from a script running on a remote computer. The unit

doesn’t allow setting of local SNMP traps.

Specifications













Advertising