Maui_manual_19, Table 7.6: summary of vertical venting options – Crown Boiler MWC116ENT User Manual

Page 19

Advertising
background image

17

Permitted Terminals for Vertical Venting

6)

- Use Crown PN 230532

with the appropriate flashing (Table 7.3b)

Vertical Vent Terminal Locations (Vent Option 5)

7)

- Observe the following limitations on the location of all

vertical vent terminals (see Figure 7.7):

The top of the vent pipe must be at least 2 feet above any object located within 10 feet.

•

The bottom of the air inlet terminal must be at least 12” above the normal snow accumulation that can be

•

expected on the roof. The terminal used in Vent Option #5 has a fixed distance above the storm collar of
19”. If a greater distance is needed to provide the clearance above the snow line, build a chase on the
roof and mount the vertical terminal on top of the chase.

Wall thimbles

8)

– Concentric vent has a “zero” clearance to combustibles and therefore does not require the

use of wall thimbles.

Pitch of Horizontal Piping

9)

- Pitch all horizontal piping so that any condensate which forms in the piping will run

towards the boiler. Pitch Crown horizontal concentric venting 5/8” per foot

Supporting Pipe

10)

- Vertical and horizontal sections of pipe must be properly supported. Support Crown

concentric venting near the female end of each straight section of pipe. Exception: Vertical runs of concentric
pipe in an unused chimney (Figure 7.36) need only be supported at the terminal and at the base of the run.

Table 7.5: Vent/ Air Intake Fitting Equivalent Length

VENT FITTING

EQUIVALENT LENGTH (ft)

60/100mm 90° CONCENTRIC ELBOW

4.5

60/100mm 45° CONCENTRIC ELBOW

4.0

80/125mm 90° CONCENTRIC ELBOW

8.5

80/125mm 90° SWEEP CONCENTRIC ELBOW

5.5

80/125mm 45° CONCENTRIC ELBOW

3.0

80/125mm 90° CONCENTRIC SUPPORT ELBOW

8.5

Table 7.6: Summary Of Vertical Venting Options

VENT OPTION #

5

6

CLASSIFICATION USED IN THIS
MANUAL

VERTICAL

CONCENTRIC

RESERVED FOR

FUTURE USE

ILLUSTRATED IN FIGURE

7.7

VENT PIPE PENETRATION
THROUGH STRUCTURE

ROOF

VENT PIPE SIZE

80/125mm

CONCENTRIC

INLET AIR ORIFICE SIZE

82mm

MAX. VENT LENGTH

27ft - 10in

MIN. VENT LENGTH

6in

VENT TERMINAL

CROWN #230532

CONCENTRIC

TERMINAL (TABLE

7.3b)

VENT MATERIAL

CROWN 80/125 mm

VENT COMPONENTS

SHOWN IN TABLE

7.3b