Maui_manual_19, Table 7.6: summary of vertical venting options – Crown Boiler MWC116ENT User Manual

Page 19

Advertising
background image

17

Permitted Terminals for Vertical Venting

6)

- Use Crown PN 230532

with the appropriate flashing (Table 7.3b)

Vertical Vent Terminal Locations (Vent Option 5)

7)

- Observe the following limitations on the location of all

vertical vent terminals (see Figure 7.7):

The top of the vent pipe must be at least 2 feet above any object located within 10 feet.

The bottom of the air inlet terminal must be at least 12” above the normal snow accumulation that can be

expected on the roof. The terminal used in Vent Option #5 has a fixed distance above the storm collar of
19”. If a greater distance is needed to provide the clearance above the snow line, build a chase on the
roof and mount the vertical terminal on top of the chase.

Wall thimbles

8)

– Concentric vent has a “zero” clearance to combustibles and therefore does not require the

use of wall thimbles.

Pitch of Horizontal Piping

9)

- Pitch all horizontal piping so that any condensate which forms in the piping will run

towards the boiler. Pitch Crown horizontal concentric venting 5/8” per foot

Supporting Pipe

10)

- Vertical and horizontal sections of pipe must be properly supported. Support Crown

concentric venting near the female end of each straight section of pipe. Exception: Vertical runs of concentric
pipe in an unused chimney (Figure 7.36) need only be supported at the terminal and at the base of the run.

Table 7.5: Vent/ Air Intake Fitting Equivalent Length

VENT FITTING

EQUIVALENT LENGTH (ft)

60/100mm 90° CONCENTRIC ELBOW

4.5

60/100mm 45° CONCENTRIC ELBOW

4.0

80/125mm 90° CONCENTRIC ELBOW

8.5

80/125mm 90° SWEEP CONCENTRIC ELBOW

5.5

80/125mm 45° CONCENTRIC ELBOW

3.0

80/125mm 90° CONCENTRIC SUPPORT ELBOW

8.5

Table 7.6: Summary Of Vertical Venting Options

VENT OPTION #

5

6

CLASSIFICATION USED IN THIS
MANUAL

VERTICAL

CONCENTRIC

RESERVED FOR

FUTURE USE

ILLUSTRATED IN FIGURE

7.7

VENT PIPE PENETRATION
THROUGH STRUCTURE

ROOF

VENT PIPE SIZE

80/125mm

CONCENTRIC

INLET AIR ORIFICE SIZE

82mm

MAX. VENT LENGTH

27ft - 10in

MIN. VENT LENGTH

6in

VENT TERMINAL

CROWN #230532

CONCENTRIC

TERMINAL (TABLE

7.3b)

VENT MATERIAL

CROWN 80/125 mm

VENT COMPONENTS

SHOWN IN TABLE

7.3b