Wine-Mate SSW Series Digital Control Manual User Manual

Installing and operating instructions

Advertising
background image

Installing and Operating Instructions

Vinotemp

1/3

Digital controller with off cycle defrost and

Fan Control

CONTENTS
1.

GENERAL WARNING ____________________________________________________1

2.

GENERAL DESCRIPTION ________________________________________________1

3.

CONTROLLING LOADS __________________________________________________1

4.

FRONT PANEL COMMANDS ______________________________________________1

5.

MAX & MIN TEMPERATURE MEMORIZATION _______________________________1

6.

MAIN FUNCTIONS ______________________________________________________2

7.

PARAMETERS _________________________________________________________2

9.

TTL SERIAL LINE – FOR MONITORING SYSTEMS____________________________2

11.

INSTALLATION AND MOUNTING __________________________________________3

12.

ELECTRICAL CONNECTIONS _____________________________________________3

13.

HOW TO USE THE HOT KEY______________________________________________3

14.

ALARM SIGNALS _______________________________________________________3

15.

TECHNICAL DATA ______________________________________________________3

16.

CONNECTIONS_________________________________________________________3

17.

DEFAULT SETTING VALUES______________________________________________3

1. GENERAL WARNING

1.1 PLEASE READ BEFORE USING THIS MANUAL

This manual is part of the product and should be kept near the instrument for easy and
quick reference.

The instrument shall not be used for purposes different from those described hereunder. It
cannot be used as a safety device.

Check the application limits before proceeding.

1.2

SAFETY PRECAUTIONS

Check the supply voltage is correct before connecting the instrument.

Do not expose to water or moisture: use the controller only within the operating limits
avoiding sudden temperature changes with high atmospheric humidity to prevent formation
of condensation

Warning: disconnect all electrical connections before any kind of maintenance.

Fit the probe where it is not accessible by the End User. The instrument must not be
opened.

In case of failure or faulty operation send the instrument back to the distributor

with a

detailed description of the fault.

Consider the maximum current which can be applied to each relay (see Technical Data).

Ensure that the wires for probes, loads and the power supply are separated and far enough

from each other, without crossing or intertwining.

In case of applications in industrial environments, the use of mains filters (our mod. FT1) in
parallel with inductive loads could be useful.

2. GENERAL DESCRIPTION

Model 30 format 32 x 74 mm, is a digital thermostat with off cycle defrost designed for
refrigeration applications at normal temperature. It provides two relay outputs, one for the
compressor, the other one can be used as light, for alarm signalling or as auxiliary output.. It is
also provided with 1 or 2 NTC probe inputs the first one for temperature control, the second one,
optional, to connect to the HOT KEY terminals to signal the condenser temperature alarm or to
display a temperature. The digital input can operate as third temperature probe.
The HOT KEY output allows to connect the unit, by means of

an external module, to a network

line compatible.
It allows to program the controller by means the HOT KEY programming keyboard.
The instrument is fully configurable through special parameters that can be easily programmed
through the keyboard.

3. CONTROLLING LOADS

3.1 COMPRESSOR

The

regulation

is

performed

according to the temperature
measured by the thermostat probe
with a positive differential from the
set point: if the temperature
increases and reaches set point plus
differential the compressor is started

and then turned off when the
temperature reaches the set point
value again.

Time

Temper.

Compr.

SET

ON

In case of fault in the thermostat probe the start and stop of the compressor are timed through
parameters “COn” and “COF”.

3.2 DEFROST

Defrost is performed through a simple stop of the compressor. Parameter “IdF” controls the
interval between defrost cycles, while its length is controlled by parameter “MdF”.

4. FRONT PANEL COMMANDS

: To display target set point; in programming mode it selects a parameter or confirm an

operation.

(DEF) To start a manual defrost

(UP): To see the max. stored temperature; in programming mode it browses the parameter

codes or increases the displayed value.

(DOWN) To see the min stored temperature; in programming mode it browses the

parameter codes or decreases the displayed value.

O/I

To turn ON or OFF the controller (if enabled)


KEY COMBINATIONS:

+

To lock & unlock the keyboard.

+

To enter in programming mode.

+

To return to the room temperature display.

4.1 CONTROL OF EVAPORATOR FANS

The fan control mode is selected by means of the “FnC” parameter:
FnC = C_n: fans will switch ON and OFF with the compressor and not run during defrost;
FnC = o_n fans will run even if the compressor is off, and not run during defrost;
After defrost, there is a timed fan delay allowing for drip time, set by means of the “Fnd
parameter.

FnC = C_Y fans will switch ON and OFF with the compressor and run during defrost;
FnC = o_Y fans will run continuously also during defrost

An additional parameter “FSt” provides the setting of temperature, detected by the evaporator
probe, above which the fans are always OFF. This is used to make sure circulation of air only if
his temperature is lower than set in “FSt”.
4.1.1 Cyclical activation of the fans with compressor off.

When Fnc = c-n or c-Y (fans in parallel to the compressor), by means of the Fon and FoF
parameters the fans can carry out on and off cycles even if the compressor is switched off. When
the compressor is stopped the fans go on working for the Fon time. With Fon =0 the fans remain
always off, when the compressor is off. This increases humidity in the system.

4.2 USE OF LEDS

Each LED function is described in the following table.

LED

MODE

FUNCTION

ON

Compressor enabled

Flashing

Anti-short cycle delay enabled

ON

Defrost enabled

ON

An alarm is occurring

°C/°F ON

Measurement unit

°C/°F Flashing

Programming phase

5. MAX & MIN TEMPERATURE MEMORIZATION

5.1 HOW TO SEE THE MIN TEMPERATURE

1.

Press and release the n key.

2.

The “Lo” message will be displayed followed by the minimum temperature recorded.

3.

By pressing the n key again or by waiting 5s the normal display will be restored.