INPUT CHARACTERISTICS:

DR3G-6650P

A

INPUT CHARACTERISTICS

1

VOLTAGE

DC -36V

-72V

2

INPUT CURRENT

12A MAX.FOR EACH POWER UNIT.

3

INRUSH CURRENT

20A MAX.FOR FOR EACH POWER UNIT

B

OUTPUT CHARACTERISTICS

OUTPUT

OUTPUT CURRENT

REGULATION

OUTPUT RIPPLE &

VOLTAGE

MIN.

MAX. PEAK

LOAD

LINE

NOISE MAX. [P-P]

+5V

3.0A

60A

5%

1%

50mV

-5V

0.1A

1A

5%

1%

120mV

+12V

2A

40A

10%

1%

120mV

-12V

0.1A

1A

10%

1%

150mV

+3.3V

1.0A

40A

5%

1%

50mV

+5VSB

0.1A

2.5A

5%

1%

50mV

REMARK: 1. TOTAL CURRENT OF +5V AND +3.3V NOT EXCEED 70A

C

SPECIFICATION

1

TEMPERATURE RANGE

OPERATING 10

40

STORAGE -20

70

4

HOLD UP TIME

1.6mS MIN. AT FULL LOAD & -48VDC VAC INPUT VOLTAGE

5

DIELECTRIC WITHSTAND

INPUT/OUTPUT 1500 VAC FOR 1 minute

INPUT TO FRAME GROUND 1500 VAC FOR 1 minute

4

EFFICIENCY

65% TYPICAL

AT FULL LOAD

5

POWER GOOD SIGNAL

ON DELAY 100mS TO 500mS

OFF DELAY 1mS

6

OVERLOAD PROTECTION

110

160% MAX

7 OVER VOLTAGE PROTECTION +5V

5.7V 6.5V +3.3V 3.9V

4.3V +12V 13.3V 14.3V

8

SHORT CIRCUIT: 5V,12V,3.3V, AUTO-RECOVERED: 5VSB,-5V,-12V

9 . EMI : FCC CLASS A , CISPR 22 CLASS A

10

SAFETY

UL 1950, CSA 22.2 NO/950, TUV IEC 950

11

REMOTE ON / OFF CONTROL

12

FAULTY ALARM METHODS: LED, BUZZER, TTL SIGNAL

13

2 +1, HOT-SWAPPABLE / HOT PLUGGABLE REDUNDANCY FUNCTION

14

N +1 BALANCE LOAD SHARING DESIGN ON 5/12/3.3V CHANNEL

15

REMOTE SENSING DESIGN

16

ISOLATION: BUILT-IN THE POWER MODULE

17

DIMENSION

82*127*276 (H*W*D)mm W/O FAN

82*127*300 (H*W*D)mm W/FAN

18

COOLING: THREE 40mm DC FANS (ONE IN EACH MODULE)

Advertising