INPUT CHARACTERISTICS:

R2G-6300P

VOLTAGE: 95 ~264 VAC FULL RANGE

FREQUENCY : 47 ~ 63 Hz

INPUT CURRENT: 6.0 / 3.0 A FOR 115 / 230 VAC

INRUSH CURRENT: 60A / 80A MAX. FOR 115 / 230 VAC PER POWER MODULE

OUTPUT CHARACTERISTICS:

OUTPUT CURRENT

REGULATION

OUTPUT

MIN.[A] MAX.[A] PEAK(A)

LOAD

LINE

5V

3.0

32

±

5%

±

1%

50mV

12V

2

16

20

±

6%

±

1%

120mV

-5V

0.05

0.5

±

10%

±

1%

120mV

-12V

0.05

0.8

±

10%

±

1%

150mV

3.3V

1.0

20

±

5%

±

1%

50mV

+5VSB

0.1

1.5

±

5%

±

1%

50mV

OUTPUT

VOLTAGE

RIPPLE & NOISE

MAX. [P-P]

REMARKS: TOTAL CURRENT OF +5V AND + 3.3V NOT EXCEED 32 A

TOTAL +5V AND 3.3V AND 12V POWER NOT EXCEED 285 W

.

TEMPERATURE RANGE : OPERATING 0

0

C --- 40

0

C, STORAGE –20

0

C --- 80

0

C

HOLD UP TIME: 16 ms MINIMUM AT FULL LOAD & NORMAL INPUT VOLTAGE

DIELECTRIC WITHSTAND: INPUT / OUTPUT 1500 VAC FOR 1 MINUTE

INPUT TO FRAME GROUND 1500 VAC FOR 1 MINUTE

EFFICIENCY: 63% TYPICAL, AT FULL LOAD

POWER GOOD SIGNAL: ON DELAY 100 ms TO 500 ms, OFF DELAY 1 ms

OVER LOAD PROTECTION: 110 ~ 160% MAX.
OVER VOLTAGE PROTECTION:
+5V

5.7V ~ 6.5V, 3.3V

3.9 ~ 4.3V, 12V

13.3 ~ 14.3V

. OVER CURRENT PROTECTION : 5V, 12V, 3.3V 130% +/- 20% AT FULL LOAD
-5V, -12V SHORT CIRCUIT

EMI NOISE FILTER: FCC CLASS B, CISPR22 CLASS B

SAFETY: UL 1950, CSA 22.2 NO/ 950, TÜV IEC 950

REMOTE ON / OFF CONTROL

FAULTY ALARM METHODS : LED, BUZZER, TTL SIGNAL

HOT-SWAPPABLE / HOT-PLUGGABLE REDUNDANCY FUNCTION

BALANCE LOAD SHARING DESIGN

REMOTE SENSING DESIGN

ISOLATION: BUILT-IN IN THE POWER MODULE

MEET IEC-1000-3-2 CLASS D ( ACTIVE PFC )

DIMENSION: 82(H) X 101(W) X 300 (D) mm W Rear DC Fan

82(H) X 101(W) X 276 (D) mm W/O Rear DC Fan

COOLING : TWO 40 mm DC FANS ( ONE IN EACH MODULE )

ONE 80 mm DC FAN (REAR SIDE)

* I2C FEATURE (OPTIONAL )

Revision: A05