Page 51

BRUTE ELITE

label and turn on the gas and electrical power to the
appliance.

4.

The Brute Elite unit will begin the start sequence.

The blower and pump will energize for the pre-purge
period, then the ignition sequence will start. After

all safety devices have been verified, the gas valve
will open. If ignition doesn’t occur, turn off the Brute

Elite, and check that there is proper gas supply. Wait 5
minutes before restarting.

5.

Turn the Brute Elite on.

6.

After placing the appliance in operation, the Burner

Safety Shutoff Device must be tested:

Close the gas shutoff valve with the burner operating.

The flame will go out and the blower will

continue to run for the post purge cycle. One
or three additional attempts to light will follow.

Each cycle will include pre-purge, ignitor on,

valve/flame on, and post purge. Ignition will not
occur because the gas is off. The ignition control
will lockout.

Open the gas shutoff valve. Reset the boiler
control by pressing the Reset button on the
control or on the display. Restart the appliance.
The ignition sequence will start again and the
burner will start. The appliance will return to its
previous mode of operation.

DANGER

If you detect any odor of gas, or if the gas burner

does not appear to be functioning in a normal

manner, CLOSE THE MAIN SHUTOFF VALVE.

Do not shut off the switch. Contact your heating

contractor, gas company, or factory representative.

9.3 Adjusting CO

2

1.

Measure the CO

2

/O

2

in the flue products at

high fire.

The Brute Elite can be forced to high fire to allow for
easier setup. The controller has a feature that makes it

easy to go directly to the high fire condition. The unit

will operate at high fire for 5 minutes, then modulate
down automatically.

How to get there: From the “Home” screen,

press “I” to go to “Info/ Install.” Choose “Test,” then

go to “Forced Rate.” Select “Set High Fire,” then

select “Start Test.”

The CO

2

readings should be between the values shown

in Table 15 R or Table 15 C. If the CO

2

is not within

the range shown, adjustments may be made. To adjust

the high fire CO

2

, locate the high fire adjuster screw

according to the appropriate figure. Slowly make

adjustments in 1/16 of a revolution increments until the

CO

2

is within the range identified.

2.

Measure the CO

2

/O

2

in the flue products at

low fire.

Brute

Elite can be forced to low fire to allow for easier setup.

3.

Repeat steps 1 and 2 to confirm that the CO

2

ranges are

within the required ranges. Adjust if necessary.

4.

Confirm that the differential pressure is still within the
appropriate range.

5.

If any of the measurements cannot be adjusted to the

specified ranges or the CO levels are above 150ppm
when adjusted, please consult the factory for further
information.

WARNING

Improper adjustment may lead to poor combustion

quality, increasing the amount of carbon monoxide

produced. Excessive carbon monoxide levels may

lead to personal injury or death.

Table 15 C (Commercial, sizes 399 - 850 Mbtu)

CO

2

Range and Manifold Pressure

GAS TYPE

HIGH FIRE, CO

2

LOW FIRE, CO

2

DIFFRNTL PRESSURE

(

inches wc)

Natural

8.8 to 9.8%

0.5% lower than

3.6” to 3.9”

Propane

9.8 to 10.2%

high fire setting

Table 15 R (Residential, sizes 80 - 285 Mbtu)

CO

2

Range and Differential Pressure

How to get there: From the “Home” screen, press

“I” to go to “Info/ Install.” Choose “Test,” then go

to “Forced Rate.” Select “Set High Fire,” then select

“Start Test.”

The CO

2

readings should be between the values shown

in Tables 15 R or Table 15 C. If the CO

2

is not within

the range shown, adjustments may be made. To adjust

the low fire CO

2

, locate the low fire adjuster screw

according to the appropriate figure. Slowly make

adjustments in 1/16 of a revolution increments until the

CO

2

is within the range identified.

GAS TYPE

HIGH FIRE, CO

2

LOW FIRE, CO

2

MANIFOLD

PRESSURE

Natural

8.8 to 9.0%

0.5% lower than

-.005” to

Propane

9.8 to 10.0%

high fire setting

-.015” wc

Advertising