PRODUCT SUPPORT 800.927.2120 8am - 6pm EST

HENRY

THERMOSTATIC VALVE

INSTALLATION GUIDELINES

Page 2 of 3


5.15.2014

These guidelines have been prepared for the professional contractor to aid in the installation of:
HENRY THERMOSTATIC VALVE STYLE NO. GUTH47, GU47TH (UK)
All dimensions are based on original specification and are subject to change and variation.
Please consult your Design Associate for current specifications.

¾ See Figure - 03 for steps 3-6.

3. Run 3/4" (22mm) copper supply lines to the proper

height of the valve inlets and be sure to secure all
piping and fittings.


4. This valve includes VOLUME CONTROLS or ON/OFF

VALVES to control each fitting that will have water
flowing to it.

5. Install the TILE GUARD to protect the valve during

the completion of the finished wall and to create the
exact opening for access to the service stops and
future servicing.

3/4" (22mm)

COLD SUPPLY

OUTLET TO

SHOWER

FITTING

VOLUME CONTROL

ON/OFF VALVE

THERMOSTATIC VALVE

(FLUSH PLATE

PRE-INSTALLED)

3/4" (22mm)

HOT SUPPLY

VOLUME CONTROL

ON/OFF VALVE

OUTLET TO

SHOWER

FITTING

TILE

GUARD

3/4" (22mm)

COLD SUPPLY

OUTLET TO

SHOWER

FITTING

VOLUME CONTROL

ON/OFF VALVE

THERMOSTATIC VALVE

(FLUSH PLATE

PRE-INSTALLED)

3/4" (22mm)

HOT SUPPLY

VOLUME CONTROL

ON/OFF VALVE

OUTLET TO

SHOWER

FITTING

TILE

GUARD

FIGURE - 03

FLUSH OUT THE SYSTEM:

¾ Before installing the cartridge, the supply lines must

be flushed out to prevent clogging of the filter
screens. Failure to flush the lines will permanently
damage the cartridge and void the warranty. Repeat
this process as needed prior to trim installation.

¾ See Figure - 04 for steps 6-10.

6. The VALVE BODY is shipped with the FLUSH PLATE

pre-installed, and is ready for flushing the lines.


7. Turn on the water supply and open the SERVICE

STOPS to flush out the lines then inspect all
connections for leaks.

8. After the lines are flushed, turn off the water supply

and close the SERVICE STOPS, unthread the 2 cover
SCREWS, then remove the FLUSH PLATE.

9. Install the CARTRIDGE using the 2 cover SCREWS

and turn off the SERVICE STOPS.

ROUGH-IN:

1.

Make sure the valve body is positioned according to
valve markings so the inlets are situated with hot
piped on the left and cold piped on the right. See
Figure - 01.

VOLUME CONTROL

ON/OFF

VOLUME CONTROL

ON/OFF

FLUSH PLATE

PRE-INSTALLED

VOLUME CONTROL

ON/OFF

VOLUME CONTROL

ON/OFF

FLUSH PLATE

PRE-INSTALLED

H

C

5-11/16"

(144.5mm)

CENTER

OF INLETS

5-11/16"

(144.5mm)

13/16"

(21mm)

OUTLET

TO SHOWER

FITTING

OUTLET

TO SHOWER

FITTING

FIGURE - 01

2. IMPORTANT: Valve rough-in depth is measured

from the center of the inlets to the surface of the
finished wall and varies depending on the trim used.
See Figure - 02

FINISHED

WALL

FLUSH PLATE

PRE-INSTALLED

FINISHED

WALL

FLUSH PLATE

PRE-INSTALLED

CENTER

OF INLETS

ROUGH-IN DEPTH

2-1/8" MIN - 3-1/8" MAX

(54mm MIN - 79mm MAX)

FIGURE - 02