1 – function, 5 – pressure connection, 2 – enclosure – Pilgrim MULTIFUNCTION PRESSURE AND TEMPERATURE SWITCHES User Manual

Page 5: 4 – actuator seal, 7 – nominal range, 3 – switch elements for gpa/lpa, gda/lda controls, 6 – g-, l-series pressure switch options

Advertising
background image

5

NOTES:

1. These items are wetted by process fluid.

2. Ambient operating temperature limits -20 to 150

°

F,

all styles. Setpoint shift of

±

1% of range per 50

°

F temperature

change is normal.

3. Estimated dc rating, 2.5A, 28 Vdc (not UL listed).
4. Estimated dc rating, 4A, 28 Vdc (not UL listed).
5. Not UL listed at 480 Vac.
6. Standard on G Series “H

2

O ranges

7. Supply static pressure for D/P switches.
8. Stainless steel diaphragm only.
9. Not available with Buna-N diaphragm.
10. Available with LPS and LDS models.
11. LPS, Buna N and Viton diaphragm only.
12. LPS, stainless steel diaphragm only.
13. Available on pressure models only.
14. Order switch and 15-320SX-02T CG seal.
15. Order switch and 20-320SX-02T CG seal.

1 – FUNCTION

GPS/LPS - Pressure control, single setpoint,

fixed deadband.

GPA/LPA - Pressure control, single setpoint,

adjustable deadband.

GPD/LPD - Pressure control, two indepen-

dently adjustable setpoints, fixed
deadband.

GDS/LDS - Differential pressure control, single

setpoint, fixed deadband.

GDA/LDA - Differential pressure control, single

setpoint, adjustable deadband.

GDD/LDD -Differential pressure control, two

independently adjustable setpoints,
fixed deadband.

5 – PRESSURE CONNECTION

(1)

Order Code

25

1

⁄

4

NPT Female

Standard on Pressure
and D/P

1

⁄

4

NPT Female and

06

1

⁄

2

NPT Male Combination

Pressure Only

07

1

⁄

2

NPT Female

Pressure Only

G and L SERIES PRESSURE SWITCH AND DIFFERENTIAL
PRESSURE SWITCH ORDERING INFORMATION

2 – ENCLOSURE

N4 - NEMA 4, 4X

L Series: Epoxy Coated, Die Cast
Aluminum, IP66
G Series: 316 SS IP65

4 – ACTUATOR SEAL

(1)

Code

Process

Range

&

Temp.

(2)

Vac

0-600 1000 2000-

Material

Limits

"H

2

O

psi

psi

3000

°

F

psi

B-Buna-N

0 to 150

●

●

●

●

V-Viton

20 to 300

●

●

●

T-Teflon

0 to 150

●

●

●

●

S-St.St

(13)

0 to 300

● ●

P-Monel

(13)

0 to 300

●

7 – NOMINAL RANGE

See page 4

SWITCH ELEMENTS FOR FOR GPD/LPD,
GPS/LPS, LDD/GDD & LDS/GDS CONTROLS

Code

Switch elements

Single Dual

UL/CSA listed

(PS) (PD)

K

(4)

KK

Narrow deadband

15A, 125/250 Vac

F

(4)

FF

Sealed environment 15A, 125/250 Vac
proof

15A, 125/250/480 Vac

G

(5)

GG

General purpose

1/2A, 125 Vdc
1/4A, 250 Vdc

Hermetically sealed

P

(3)

PP

switch, narrow

5A, 125/250 Vac

deadband

Hermetically sealed

J

JJ

switch, general

11A,125/250 Vac

purpose

5A, 30 Vdc

3 – SWITCH ELEMENTS FOR GPA/LPA,
GDA/LDA CONTROLS

Description/Maximum Electrical Ratings

Code

UL/CSA listed

10A,125/250 Vac

H

General purpose

1/2A, 125 Vdc
1/4A, 250 Vdc

Hermetically sealed

J

switch, general

11A, 125/250 Vac

purpose

5A, 30 Vdc

6 – G-, L-SERIES PRESSURE SWITCH OPTIONS

Available

Differential

Series

Pressure

Pressure

Code

Description

G

L

psi

˝H

2

O

psid

˝H

2

O

XCH

Chained Cover

•

•

•

•

•

•

XFP

Fungus Proof

•

•

•

•

•

•

XFS

(7)

Factory-Adjusted Setpoints

•

•

•

•

•

•

XG5

(11)

Gas/Oil

UL Limit Control to 150 ˝H

2

O

•

•

LDS only

XG6

(13)

Gas/Oil

UL Limit Control to 600 psi

•

•

LPS only

XG8

(12)

Steam Limit Control to 300 psi

•

•

XG9

(8)

Fire Safe Actuator

•

•

High Operating Pressure for H

2

O

Ranges:

XHX

40 PSI Static (Pressure and D/P)

•

•

•

•

100 PSI Proof (Pressure)
160 PSI Proof (D/P)

XJL

3

/

4

˝ to

1

/

2

˝ Reducing Bushing

•

•

•

•

•

•

XK3

Terminal Blocks

•

•

•

•

•

•

XNH

Tagging Stainless Steel

•

•

•

•

•

•

XPK

Pilot Lights

•

•

•

•

•

XPM

3

/

4

˝ Sealed Conduit Connection

with 16˝ Lead Wires

•

•

•

•

•

•

XTA

(6)

316SS Pressure Connection
for ˝H

2

O Ranges

•

•

•

•

XUD

316SS Pressure Connection
for psiD Ranges

•

•

•

X2C

(10)

DPDT with Single Setpoint
Adjustment

•

•

•

•

•

•

X6B

(9)

Cleaned for Oxygen Service

•

•

•

•

XFM

FM Approval

•

•

•

•

•

X3A

1

1

/

2

˝ Sanitary Seal with Glycerin Fill

(14)

• •

2˝ Sanitary Seal with Glycerin Fill

(15)

•

•

XHS High Static Operating Pressure
for PSI Range D/P • •

•

1

2

3

4

5

6

7

G

P D N 4 G G B 2 5 X K 3 30 PSI

Advertising