• With 18 alarms interconnected, it is still possible to interconnect up to

a total of six remote signaling devices and/or relay modules.

• The maximum wire run distance between the first and last unit in an

interconnected system is 1000’ (305 m).

• Make certain alarms are wired to a continuous, (non-switched) power

line. NOTE: Use standard UL Listed household wire (as required by
local codes) available at all electrical supply stores and most hardware
stores.

Wiring

The diagram above illustrates interconnection wiring. Improper connec-
tion will result in damage to the alarm, failure to operate, or a shock
hazard.

CAUTION: Turn off the main power to the circuit before wiring
the alarm.

Wires on the AC Quick-Connector Alarm Harness:

Black

Connected to live (L) side of AC line

White

Connected to neutral (N) side of AC line

Red

Connected to interconnect lines (red wires) of other units
in a multiple-station set-up

4. Installation Instructions

FUSE OR CIRCUIT BREAKER

RED

BLACK

WHITE

CONNECTOR

First CO Alarm

Additional

CO Alarm

Optional

Accessory

(See list of compatible

Kidde devices)

Interconnect Wiring Diagram