Beckett AquaSmart Wiring User Manual

Page 42

Advertising
background image

42

Technology Made Simple.

Direct Replacement of Honeywell L7224U with AquaSmart A

Legend

1 - Neutral / White

2 - Hot / From Low Water Cut Off

3 - Red / To Thermostat

4 - White / To Thermostat

5 - Hot / To Circulator

6 - Neutral / To Circulator

7 - Hot / To Burner Ignition

8 - Neutral / To Burner Ignition

9 - Ground

Notes on AquaSmart:

1. Set control to match determined High Limit or

Low Limit application.

2. Terminals ZC and ZR are not used in this

application.

3. If using the 2-in-1 probe, the hot to L1 will be

supplied from Service Switch. Also remove
current Low Water Cut Off

.

AquaSmart Settings:

High Limit: 180

High Differential: 10

Low Limit: “OFF”

Set DHWP to “OFF”

Low Limit: 160 (with Tankless H/W Coil)

Low Differential: 10

Set Circulator on “TT”

Circulator On-Delay: 30 Seconds

Circulator Off-Delay: 4 Minutes

Set Economizer to “ON”

• Set

Effi ciency “HI”

1