Beckett, 12 vdc oil igniter – Beckett 61828 12V Oil Igniter User Manual

Page 2

Advertising
background image

R.W.

BECKETT

CORPORATION

P.O. Box 1289, Elyria, Ohio 44036

R.W. BECKETT CANADA, LTD

430 Laird, Unit 3, Guelph, Ontario, N1G 3X7

12 Vdc Oil Igniter

Table 2 - Igniter Base Plate Bill of Materials

Part No.

Burner Models

Baseplate

Gasket

Baseplate

Igniter

Gasket

Barrier

Gasket

5218301U

Beckett ADC 12 Vdc

31405

51780BK

32743

32301*

5218303U

Beckett SDC 12 Vdc

31481

51855BK

32743

n/a

5218307U

Wayne ‘M’ Models for 12 Vdc

n/a

51899BK

n/a

n/a

5218305U

Wayne ‘E’ Models for 12 Vdc

n/a

21847

n/a

n/a

* 32301 Barrier Gasket is used only on Beckett Model ADC.

Figure 1 - Igniter Assembly Components (5218301U shown. Other models will have different baseplates and terminals.)

Baseplate Gasket

Baseplate

Igniter

Mounting Screws

3241101 Igniter Gasket

(Between baseplate and igniter)

Igniter Input (+) Blue-White Striped Lead

Field Installed Cad Cell
(if applicable)

Barrier Gasket

Yellow Leads For Cad Cell Connection -

Interrupted Ignition Without Primary Control

The Yellow leads from the igniter will NOT be used and shall
be wire nutted individually and placed in the housing wiring
compartment.
Verify the igniter secondary output terminals are correctly
arranged to make good electrical contact with the oil burner
electrodes.

16.

17.

Igniter Input (+) Solid White Spark Control Lead

Igniter Input (-) Black Lead for Ground

Yellow Cad Cell Leads

Close the igniter. Install and securely tighten the two front
base plate retaining screws (4 screws, if no hinge).
Reconnect electric power to the burner circuit.
Verify with instruments that the burner is adjusted to the
manufacturer’s recommended settings
Cycle the burner several times to verify prompt and smooth
ignition. Verify proper operating and limit control operation
before leaving.

18.

19.
20.

21.

Advertising