EdgeAccess Universal Chassis System

Model 1202 CIM User Manual

3-2

Field Definition

Backplane Alarm Inputs Shows fault conditions in a module in this chassis or in a linked CIM

CIM Major Alarms
CIM Minor Alarms

Shows detected Major or Minor alarm conditions

Up Link Installed
Down Link Installed

Shows connections to other CIMs

CIM Model
CIM Firmware
CIM Serial Number
CIM Hardware Version

Lists configuration data

Note: If Alarm Relay Status is Major or Minor and Alarm Latch Status is off, the alarm

condition occurred on a linked chassis.

3.2 Using

Alarm

Information

All modules in the chassis route alarms to the CIM. In addition, the CIM generates alarms for
internal faults. The CIM forwards the alarms to the MAJ or MIN LEDs and the alarm relays.

These conditions cause a Major alarm:

• Recovery from total power failure
• Power failure in a linked CIM
• A major alarm in a module in the chassis

These conditions cause a Minor alarm:

• Failure of one power supply in a redundant power supply configuration
• Failure of the clock signal on the CIM
• A minor alarm in a module in the chassis

If an alarm occurs in a linked chassis configuration, look for the chassis with the amber STA
LED; that chassis is generating the alarm.

When a CIM in a link loses power, it signals both major and minor alarms to the external devices.
However, the link between chassis does not break unless the link cables are unplugged.

To reset the alarm relays after resolving the cause of an alarm, access the CIM Management
screen, type

1

, Reset Major and Minor Alarm Relay, and press <Enter>.

For information on alarms in other modules in the chassis, see the users manual for the module.