Steffes Transmitter User Manual

Page 7

Advertising
background image

D

IP

S

WITCH

S

ETTINGS

C

ONTINUED

….

DIP SWITCH 6: NOT USED IN PLC TRANSMITTER

FACTORY DEFAULT SETTING = OFF

DIP SWITCH 7: NEGATIVE OUTDOOR TEMPERATURE

CALIBRATION

This dip switch is used to calibrate the outdoor temperature sensor

information

DOWNWARD if it is reading HIGHER than the actual

outdoor temperature.

FACTORY DEFAULT SETTING = OFF

Off = Standard operating position.

On =

A negative 5

o

F (-5

o

F) outdoor temperature calibration will be applied.

DIP SWITCH 8: POSITIVE OUTDOOR TEMPERATURE

CALIBRATION

This dip switch is used to calibrate the outdoor temperature sensor

information

UPWARD if it is reading LOWER than the actual outdoor

temperature.

FACTORY DEFAULT SETTING = OFF

Off = Standard operating position.

On =

A positive 5

o

F (+5

o

F) outdoor temperature calibration will be applied.

I

NSTALLATION

C

ONTINUED

Outdoor Temperature Sensor

The outdoor sensor provides outdoor temperature information to the

transmitter which in turn sends these signals, wireless, to the microprocessor

based heating systems. The heater’ s brick core temperature target level

adjusts automatically in relation to outdoor temperature.
A temperature sensing thermistor is connected to the two “OS” positions of

the low voltage terminal strips for automatic charge control of ETS heaters.

This sensor can be utilized if the transmitter is mounted in a location where it

can accurately sense the outdoor temperature and will not be affected by

direct sunlight or other sources of heat and cold. The temperature sensor may

be affected by heat generation from inside the enclosure. However, in most

applications, it provides suitable outdoor temperature sensing.

If the transmitter is installed indoors and automatic charge control

is desired, a remote outdoor sensor is required. This outdoor

sensor connects to the two "OS" positions of the low voltage

terminal strip in the transmitter. The existing thermistor MUST

be removed before connecting a remote mounted outdoor sensor.

Indicator Light

When the circuit board is energized, the indicator light should always

illuminate, either in a flashing mode or in a continuous illumination mode, to

indicate the microprocessor is processing information. The various

illuminations of this light are described below:

No Illumination: The microprocessor is unable to process information.

Check for proper system wiring.

Continuous Illumination: Will occur anytime a peak control signal is

being received.

Slow Flash (4 second duration): Will occur during off-peak times.

The illumination time of the light is in direct relation to the temperature

information the transmitter is receiving from the outdoor temperature

sensor. A long illumination time indicates warmer temperatures and a

short illumination time indicates colder temperatures.

Room Temperature Set Back

If using the PLC transmitter with the Steffes microprocessor based heating

equipment and utilizing the automatic room temperature set back option, the

addition of a signaling device is required to initiate the set back time. This

signaling device connects to the “R” and “E” input positions of the terminal

strip in the transmitter. When the transmitter receives the set back signal, it

sends that signal, wireless, to the heater(s). The heater(s) respond by

maintaining the set back temperature programmed into them. A closed

switch indicates room temperature set back is enabled.

6

3

Advertising