Installation and Operation Manual

8

BATTERY CHARGE PARAMETERS Menu

‘

From Setup menu













































FIGURE 5

SET ACCEPT CHG
14.4V SEL

►

Sets Acceptance charge voltage setpoint.
Range 10.0 to 80.0V.

SET FLOAT CHG
13.4V SEL

►

Sets Float charge voltage setpoint.
Range 10.0 to 80.0V.

SET ACCEPT TIME
2.0HRS SEL

►

SET FLOAT CURENT
1.5A/100AH SEL

►

Sets Float Transition Current. Range 0.1 to 10.0A per 100 AH. A setting of 0 (zero)
disables function such that full charge is based on acceptance charge time only.
See charge controller operators manual.

SET EQUALIZ CHG
15.2V SEL

►

Sets Equalize voltage setpoint.
Range 10.0 to 80.0V.

SET EQUALIZ TIME
2.0HRS SEL

►

Sets Equalize time.
Range 0.5 to 10 hours.

SET AUTO EQUALIZ
30DAYS SEL

►

Sets days between automatic Equalize. Range is 10 to 400 days. Fully MANUAL
equalization is selected by a setting of less than 10 days.

SET T-COMP SLOPE
-5.00mV/C/C SEL

►

Sets charge voltage temperature compensation factor. Range is -0.00 to -
8.00mV/

°C/cell.

Sets Acceptance charge time.
Range 0.0 to 10.0 hours.