7 | accessories – GEA Bock F18 User Manual

Page 22

Advertising
background image

22

D
GB
F
E

96246-07.2014-DGbRu

WARNING

Several capacity regulators cannot switch at the same time during
compressor operation! Otherwise the sudden change in load can
damage the compressor! Comply with the switching interval of 60 s.

Comply with the switching sequence:

Swiching

on LR1 60s LR2 60s LR3

Swiching off

LR3

60s

LR2

60s

LR1

7.1 Capacity regulator

7| Accessories

ATTENTION If the capacity regulator is mounted at the factory, the control com-

ponent (pilot valve) is mounted and connected subsequently by the
customer. If the control component is not connected, the cylinder bank
is switched off permanently. Damage to the compressor is possible!

Delivery status (ex works):
Capacity regulator assembled with cover
(transport protection).

Fig. 22

Fig. 23

LR 3

LR 1

LR 2

Cover

Fig. 24

Screw in control unit (pilot valve) with seal
ring and tight with 30 Nm.
Insert magnetic coil, fasten it with knurled
nut and connect it.

Fig. 25

Before start-up, remove the cover at the capacity
regulator and replace it with the enclosed control
unit (pilot valve).
Caution! The compressor is under pressure!
Depressurize the compressor first.

Control unit
(Pilot valve)

Magnetic coil

Knurled nut

Seal ring