Technical Specifications:

Dimensions (housing):

6.38" x 3.60" x 1.10"


Weight:

6.9

oz.


Environmental:

Operating

temperature:

32

°

-120

°

F (0

°

-50

°

C)

Relative Humidity:

95% (non-condensing)


Electrical:

Power Requirement:

11-14 VDC

Power Consumption:

130mA (max, relays activated)

Typical:

40mA

(quiescent)

FA404R output relay

Form C, 1A @ 28VDC, 0.5A @ 30VAC (resistive)

Receiver:

Type:

frequency-hopping spread spectrum

Operating frequency:

902-928 MHz


The

VALID DECODE LED

indicates transmissions from transmitters programmed to the receiver.


The receiver programs transmitters with the following fixed parameters:

No EOL resistor.

No Internal Contact. (The FA404 and FA404R will not support the FA200W or FA210W widegap
internal magnet contact.)

60-second supervisory check-in. (The transmitter sends a supervisory signal every 60 seconds. Some
transmitters check in at 150-second intervals.) The receiver, with a fixed 4-hour supervisory window,
will declare a programmed point inactive if no transmission is received during every 4 hour window.

The Fault Output is Latching for low battery or tamper faults. It is Follower for Inactive faults.

The Alarm Output is user-selectable to be follower, momentary, latching or toggle.


Note: FA transmitters have non-volatile memory. It is not necessary to reprogram transmitters after losing
power or changing batteries. Press the transmitter reset button to restore programming.

Installation:

Power: Supply power and ground to terminals marked 13.6V and GND on the terminal block.

Mounting: Use supplied hardware to attach FA404 or FA404R housing to wall or surface. To route wiring

out the back of the unit, use a small side cutter or utility knife to remove the knockout in the housing base.

Opening the housing:

ACTIVATED

TAMPERED

LOW BATTERY

INACTIVE

Frequency Agile

Receiver

by Inovonics Corporation

Insert a small flat screwdriver
behind pry point indicator nubs
on top or bottom of the housing
cover (4 places). Gently pry or
twist the housing cover apart.

Reset Button Access Cover:
Insert small screwdriver
in slot on left side. Hold cover
lightly while prying. Install by
inserting top latch and
snapping in at bottom.

Advertising