Power supply: A 14VAC transformer must be provided by the user to power the FA575.

Backup battery: An optional 1.2AH battery can be mounted in the FA575 enclosure.

Low voltage detection: The repeater will report low voltage if the supply voltage (either primary or backup)
causes its DC input voltage to drop below its low voltage threshold.

• AC power failure will not be reported directly—the system will detect inactivity if repeater power is off for

the duration of the supervision window. ‘

Supervision: The repeater should be programmed to send check-in signals to the receiver, but can operate
unsupervised.

To program for supervision: When programming the system panel to supervise the repeater, the repeater
point should be programmed as a 24-hour point. This is because the repeater may be processing signals from
24-hour points and should be given this same level of point status monitoring.

When programming the repeater for supervision, it is necessary to program the repeater to send check-in sig-
nals. All other programming options other than check-in times (like normally open versus normally closed, and
presence or absence of EOL resistor) will be ignored. Repeater programming is accomplished by connecting a
programming cable to the programming header on the repeater, setting the appropriate check-in time when
prompted by the panel or receiver display device, and pressing the repeater’s Reset button. (See panel or
receiver programming or installation manuals for more specific information.)

Test Button: The Test Button is used only in unique OEM applications.

Tamper: Case tamper is provided.

•

"AC POWER" and "BACKUP POWER" LEDs show
repeater power source.

•

"DECODING" indicates that the repeater is
receiving RF energy.

•

"TRANSMITTING" indicates that the repeater is
transmitting.

Note: The repeater does NOT decode while

transmitting.

•

"NOT ACTIVE" means that the repeater has not
received an Inovonics transmission within its pro-
grammed check-in interval. It is "waiting" for
incoming traffic.

Note that when power is first applied or when the
repeater reset button is pressed, the "
NOT ACTIVE"
LED will be on until the first valid transmitter message
is received.

This is a useful diagnostic indicator. In installations
where the repeater services many transmitter mes-
sages, illumination of the "
NOT ACTIVE" LED might
indicate a repeater receiver problem.