VI. SET-UP

For the 4-20 mA Input Box to be set up, current count values for two different tank volumes must be known or
recorded. The values can be determined by:

• Using the values provided by the factory

• Using the ORB to obtain a current reading of the device

TO OBTAIN A CURRENT COUNT READING – FOR ORB SOFTWARE VERSION 2.3

1. Log into the ORB normally

2. Choose Manage Devices

3. Click on one of the 4-20 mA names listed

4. Click ‘Get Current ADC Value’

5. Record the value calculated

6. Add or remove material from the vessel

7. Repeat steps listed above when material is now empty/full depending on when the first reading was taken.

8. Record second value.