Valve orientation, Valve wiring – AERCO Belimo Motorized Valves Installation User Manual
Page 5

PR2: 08/02/12 Page 5 of 20
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
Installing Belimo Motorized Valves on AERCO Benchmark Boilers
Technical instruction Document
TID-0028_0C
Figure 2: Multiple Boiler Piping Schematic Showing Motorized Valve Locations for
AERCO KC1000 Boilers
3. Valve Orientation
The valve can be oriented in any position as long as the actuator does not go below the horizontal plane.
See orientation guide from Belimo that is attached to the valve.
4. Valve Wiring
See
Table 1 on the next page to determine which of the included diagrams to use.
IMPORTANT NOTE!
The valves are supplied with 3 feet of power cable (exception:
Valve PN 92084-7 is supplied with Screw Terminal for electrical
connection) and 3 feet of auxiliary switch cable. If the cables are
not long enough, we recommend that a distribution box be
connected. The power and auxiliary cables are permanently
connected to the valve and cannot be removed.