MAINTENANCE

5. Next, loosen and remove the ignitor-injector

from the burner housing using a 1" open-end
wrench.

6. Check the ignitor-injector for evidence of

erosion or carbon build-up. If there is
evidence of substantial erosion or carbon
build-up, the ignitor-injector should be
replaced. If carbon build-up is present, clean
the component using fine emery cloth.
Repeated carbon build-up is an indication
that the combustion settings of the unit
should be checked. Refer to Chapter 4 for
combustion calibration procedures.

7. Prior to reinstalling the ignitor-injector, a high

temperature, conductive, anti-seize com-
pound must be applied to the threads.

NOTE

If a replacement ignitor-injector (part no.
58023) is being installed, a compression
nut containing a built-in ferrule will be
included with the replacement part. If
needed, 3 indexing washers are also
included. These washers may be needed
to properly position the gas injector tube
of the ignitor-injector within the 120° angle
shown in Figure 7-2.

120

120

DEG.

GAS INJECTOR TUBE

MUST BE WITHIN

THIS RANGE

IGNITOR-

INJECTOR

BURNER

HOUSING

HOUSING
CENTERLINE

Fgurei 7-2

Burner Assembly – Top View

8. Reinstall the ignitor-injector in the burner

housing and torque to 80 to 90 in-lbs.
However, if the burner housing was replaced
just prior to replacing the ignitor-injector,
torque to 180 in-lbs, then loosen and re-
tighten to 80 to 90 in-lbs.

9. Connect the staged ignition assembly to the

gas injector tube of the ignitor-injector by
securing the compression nut to the elbow of
the staged ignition assembly.

10. Reconnect the ignitor-injector cable.

11. Reinstall the side and top panels on the unit.

Table 7-1 - Maintenance Schedule

PARAGRAPH

ITEM

6 Mos.

12 Mos.

24 Mos.

Labor

Time

7.2

Ignitor-Injector

(58023)

*Inspect Inspect Replace 15

mins.

7.3

Flame Detector

(66006)

*Inspect Inspect Replace 15

mins.

7.4

Combustion

Calibration

*Check Check

1

hr.

7.5

Testing of

Safety Devices

See CSD-1

Chart in

Appendix I

20

mins.

7.6 Burner

Inspect

2

hrs.

7.7

Condensate

Drain Traps

*Inspect

Inspect &

Clean

1

hr.


* Only performed after initial 6 month period after initial startup.

7-2