Installation – AERCO BMK 3.0 LN Nat. Gas APRIL 2009 User Manual
Page 21
INSTALLATION
2-11
The combustion air must be free of chlorine, 
halogenated hydrocarbons, or other chemicals 
that can become hazardous when used in gas-
fired equipment. Common sources of these 
compounds are swimming pools, degreasing 
compounds, plastic processing and refrigerants. 
Whenever the environment contains these types 
of chemicals, combustion air must be supplied 
from a clean area outdoors for the protection 
and longevity of the equipment. 
The AERCO Benchmark 3.0 Boiler is UL listed 
for 100% sealed combustion. It can also be 
installed using room air, provided there is an 
adequate supply. (See paragraph 2.13.3 for 
more information concerning sealed combustion 
air). If the sealed combustion air option is not 
being used, an inlet screen will be attached at 
the air inlet on the top of the unit 
The more common methods of supplying 
combustion air are outlined below. For more 
information concerning combustion air, consult 
the AERCO Benchmark Venting and 
Combustion Air Guide, GF-3050. 
2.13.1 Combustion Air From Outside the 
Building 
Air supplied from outside the building must be 
provided through two permanent openings. Each 
opening must have a free area of not less than 
one square inch for each 4000 BTU/H boiler 
input. The free area must take into account 
restrictions such as louvers and bird screens. 
2.13.2 Combustion Air From Inside The 
Building 
When combustion air is provided from within the 
building, it must be supplied through two 
permanent openings in an interior wall. Each 
opening must have a free area of not less than 
one square inch per 1000 BTU/H of total boiler 
input. The free area must take into account any 
restrictions such as louvers. 
2.13.3 Sealed Combustion
The AERCO Benchmark 3.0 Boiler is UL listed 
for 100%-sealed combustion. For sealed 
combustion installations, the screen on the air 
inlet duct of the unit must be removed. The inlet 
air ductwork must then be attached directly to 
the unit’s air inlet. 
In a sealed combustion air application, the 
combustion air ducting pressure losses must be 
taken into account when calculating the total 
maximum allowable venting run. See the 
AERCO Benchmark Venting and Combustion 
Air Guide, GF-3050. When using the boiler in a 
sealed combustion air configuration, each unit 
must have a minimum 8 inch diameter 
connection at the unit.