21. If the oxygen level is not within the specified

range, adjust the level using the up (Λ) and
down (V) arrow keys on the VFD. Using the
up (Λ) arrow key will increase oxygen level
and the down (V) arrow key will decrease
the oxygen level.

22. Once the oxygen level is within the specified

range at 70%, lower the firing rate to 50%
and select VFD parameter 20. The oxygen
level at the 50% firing rate should be as
shown below.

Combustion Oxygen Level at

50% Firing Rate

Oxygen %

± 0.2

Carbon

Monoxide

NOx

7.0 %

<50 ppm

<20 ppm

23. Adjust the oxygen level as necessary to

obtain the required reading at the 50% firing
rate.

24. Next, set the firing rate to 30% and select

VFD parameter 19. The oxygen level at the
30% firing rate should be as shown below.

Combustion Oxygen Level at

30% Firing Rate

Oxygen %

± 0.2

Carbon

Monoxide

NOx

8.0 %

<50 ppm

<20 ppm

25. Adjust the oxygen level as necessary to

obtain the required reading at the 30% firing
rate.

26. Finally, reduce the firing rate to 14% and

select VFD parameter 15. The oxygen level
at the 14% firing rate should be as shown in
the following tabular listing:

Combustion Oxygen Level at

14% Firing Rate

Oxygen %

± 0.2

Carbon

Monoxide

NOx

8.5 %

<50 ppm

<20 ppm

27. Adjust the oxygen level as necessary to

obtain the required reading at the 14% firing
rate.

28. This completes the combustion calibration

procedure.

29. Return to Chapter 4, paragraphs 4.4 and 4.5

for Unit Reassembly instructions and
information on Over-Temperature Limit
Switches.