Appendix e - boiler default settings, Appendix e – AERCO BMK 3.0 LN Nat. Gas Jan 2009 User Manual

Page 85

Advertising
background image

APPENDIX E

E-1

BOILER DEFAULT SETTINGS

MENU & OPTION

FACTORY DEFAULT

Setup Menu

Password 0

Language English

Unit of Temp

Fahrenheit

Comm Address

0

Baud Rate

9600

Configuration Menu

Internal Setpt

130°F

Unit Type

Boiler

Unit Size

3.0 MBTU

Boiler Mode

Constant Setpoint

Remote Signal
(If Mode = Remote Setpoint, Direct Drive or
Combination)

4 – 20 mA / 1-5V

Bldg Ref Temp
(If Boiler Mode = Outdoor Reset)

70°F

Reset Ratio
(If Boiler Mode = Outdoor Reset)

1.2

Outdoor Sensor

Disabled

System Start Tmp
(If Outdoor Sensor = Enabled)

60°F

Setpt Lo Limit

60°F

Setpt Hi Limit

200°F

Temp Hi Limit

215°F

Max Fire Rate

100%

Pump Delay Timer

0 min

Aux Start On Dly

0 sec

Failsafe Mode

Shutdown

mA Output

Fire Rate Out

CAUTION: DO NOT Change

Lo Fire Timer

2 sec

Setpt Limit Band (If Setpt Limiting = Enabled)

5°F

Tuning Menu

Prop Band

70°F

Integral Gain

1.00

Derivative Time

0.0 min

Advertising