(b) If the KC1000 is equipped with a Siemens SSOV, remove the 1/4” NPT plug from the

downstream port on the SSOV. Connect the inlet side (flex gas hose and nipple) of the
Staged Ignition Assembly (part no. 124867) to this 1/4” NPT port as shown in Figure 21.


GAS

INLET

BLOWER

SSOV

STAGED IGNITION ASSY

FLEX GAS HOSE

CONNECT TO 1/4" NPT

DOWNSTREAM PORT

LOW PRESSURE

GAS SWITCH WITH

NPT REDUCER

KC1000 PARTIAL TOP VIEW

Figure 21. Staged Ignition Assembly Inlet Connection For Siemens SSOV


(c) For a Honeywell SSOV, remove the 1/8” plug from the inboard side of the gas cock shown

in Figure 22. Connect the inlet side of the Staged Ignition Assembly (part no. 124983)
containing the 5” long 1/8” NPT nipple to the gas cock port.