6. REFERENCE DOCUMENTS

1. Eurotherm 2000 Series Communications Handbook, # HA026230

2.

Eurotherm 2404/2408 Control Setpoint Programmer Installation and Operation
Handbook, # HA025132


7.

INTERFACING THE ECS WITH A BUILDING BAS/EMS


The ECS may be interfaced with a building’s Building Automation System (BAS) or Energy
Management System (EMS). Table 3 below shows the Modbus data addresses both for the
BAS/EMS and the AERCO ECS.

Table 3. AERCO Electronic Control System (ECS) Point Definitions

Equip. Point

Name

BAS Modbus

Data Addr

AC-106 Point

Name

Reg.

Type

Modbus Data

Addr (Hex/Dec.)

Units (Range)

Electric Valve (ECS)

01-Cntl Output
Signal

30004

OP (Control
Output Signal)

Input

0x0003 / 3

% (0 to 100)

02-Setpoint

30006

w.SP (Setpoint)

Input

0x0005 / 5

°F (40 to 180)

03-RmSetpt

40027

Remote Input
Comms Access
parameter(Setpoi
nt)

Holding

0x001A / 26

°F (40 to 180)

04-Outlet Temp

30002

Top Value (Outlet
Temp)

Input

0x0001 / 1

°F (40 to 205)

05-FBk Sensor
Temp

30290

Li1 (Feedback
Sensor Temp)

Input

0x0121 / 289

°F (40 to 180)

06-Over Temp Alarm

30075

AL 1 (Over Temp
Alarm)

Input

0x004A / 74

Enum (0,1) 0 = Safe, 1 =
Alarm

07-Flow Rate

30291

Li2 (Flow)

Input

0x0122 / 290

GPM

IMPORTANT


All Modbus addresses specified in this manual are written generically in
hexadecimal/decimal format. However, many Building Automation Systems utilize
another form of addressing where:

• 40001 is added to the generic address for a Holding Register

address.

• 30001 is added to the generic address for an Input Register

address.

Check the addressing scheme being used by the BAS interfaced to the XPC Gateway.