2 actuator installation, Figure 4-3. linkage installation details – AERCO CXT-E Retrofit Kit User Manual

Page 38

Advertising
background image

ECS and CXT-E Retrofit Instructions Kit # 27004-TAB

Technical Instruction Document

TID-0141_0A

12/30/2014

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288 Page 38 of 76

SHAFT PIN

LOCATION

LINKAGE ADAPTER

INDICATOR

PLATE

0

1

LINKAGE

ASSEMBLY

SCALE

PACKING NUT

VALVE TOP

LINKAGE

GASKET

HEX NUTS (2)

VALVE SHAFT

VALVE BODY

5

CAP SCREW

8-32 HEX NUT

(FAR SIDE)

4

INDICATOR PLATE

(CURVED END)

3

2

1

ITEM

QTY

PART DESCRIPTION

PART NUMBER

1

1

LINKAGE ASSEMBLY

24038-1 (1” TO 3” VALVES)

2

1

SCALE

59028-1 (1” VALVE)

59028-1.25 (1.25” VALVE)

59028-1.5 (1.5” VALVE)

59028-2 (2” VALVE)

59028-2.5 (2.5” VALVE)

59028-3 ( 3” VALVE)

59028-4 (4” VALVE)

3

2

8-32 HEX NUT

123322

4

2

3/8-16 X 5/8 LONG CAP SCREW

54014

5

1

GASKET

81046

Figure 4-3. Linkage Installation Details

4.1.2 Actuator Installation

Remove the Actuator Assembly (69170) from the Retrofit Kit and install as follows:

1. Depress and hold the Clutch Button (Figure 4-4) and rotate the pointer to approximately 80°

on the dial. Release the Clutch Button when properly positioned.

CAUTION

DO NOT DEPRESS THE CLUTCH BUTTON WITH POWER APPLIED
TO THE ACTUATOR

Advertising
This manual is related to the following products: