BASO BG1600M51EF-1AA User Manual

Page 12

Advertising
background image

12 BG1600M51EF-1AA Universal Intermittent Pilot Ignition Control Installation Instructions

LED Error Indications

If the control module’s internal diagnostics detect a fault it
will go into lockout. Spark and both valves will be turned
off. The LED will flash an error code .25 seconds on and
.25 seconds off for each count of the error code with
1 second off between codes. The control will remain in
this condition until power is removed by turning off the call

for heat. A flashing LED error code indicates either a
problem with wiring, or a component not working, or the
control module is faulty. Try to cycle the control again. If
the error repeats then see Table 5 for troubleshooting.

Table 5: LED Error Indications

Flash

Code

Flash Code

Description

Troubleshooting Guide

No
LED
“ON”

No Power

1.

With the MOLEX Vent Damper jumper plug installed, check for 24 volts on terminal 7
(TH) and terminal 5 (GND). If using a Vent Damper, make sure it is connected and
working and check for 24 volts on terminals 6 (24V) and 7 (TH) to terminal 5 (GND).

2.

Check for 24 volts on the secondary coil of the incoming transformer.

1

No flame in
trial time

1.

Check if the gas is turned “ON”.

2.

With the MOLEX Vent Damper jumper plug installed, check for 24 volts on terminal 7
(TH) and terminal 5 (GND). If using a Vent Damper, make sure it is connected and
working and check for 24 volts on terminals 6 (24V) and 7 (TH) to terminal 5 (GND).

3.

If no spark, check spark wire and connection to terminal 10 (SPARK) and spark ground
to terminal 4 (GND BURNER).

4.

Check if PV is wired to terminal 3 (PV) and common is wired to terminal 2
(MV/PV COM).

5.

Check for 24 volts at the PV coil.

2

Flame sense
circuit error

1.

Check Flame Sensor tip is in the flame. For proper sensing the rod tip must be
3/8”(10mm) to 1/2”(13 mm) in the flame.

2.

Check Flame Sensor circuits;

2.1. For 1 Rod Flame Sense circuit, check Spark/Flame Sensor is wired to terminal 10

(SPARK) and terminal 4 (GND BURNER). And check Jumper wire is installed between
terminal 8 (SENSE) and terminal 9 INTERN).

2.2. For 2 Rod Flame Sense circuit, check Flame Sensor is wired to terminal 8 (SENSE) and

terminal 4 (GND BURNER).

3

PV

(Pilot Valve)
circuit error

1.

Check for 24 volts on terminal 3 (PV) and terminal 2 (MV/PV COM).

2.

Check if PV is wired to terminal 3 (PV) and common is wired to terminal 2
(MV/PV COM).

3.

Check for 24 volts at the PV coil.

4

MV

(Main Valve)
circuit error

1. Check for 24 volts on terminal 1 (MV) and terminal 2 (MV/PV COM).
2. Check MV is wired to terminal 1 (MV) and common is wired to terminal 2 (MV/PV COM).

3. Check for 24 volts at the MV coil.

5

Internal
Control error

1.

Review all ground connections.

2.

Check if using fiber core resistive wire for Spark Wire.

6 to 9

Internal
Control error

1.

Software error – Restart control module.

NOTE: If the Troubleshooting Guide has been used for an error code being flashed, and the Control Module is not
working, then the Control Module maybe faulty. Replace the Control Module.