BASOTROL CE Approved Class B Shutoff Gas Valve Installation Instructions 3

Wiring

!

WARNING:

Risk of Shock.

Disconnect the power supply before making
electrical connections to avoid electrical shock or
equipment damage. Ensure that the operating
voltage is identical to the information on the product
identification label.

!

CAUTION:

Risk of Equipment Damage.

For 12 VDC, 25 VDC and 25 VAC applications, the
ground wire must not be connected to prevent
possible grounding of the 12 VDC or 25 VDC power
supply or 25 VAC transformer secondary.

The BGA171/H96 valve is supplied with 3-tab and
2-tab electrical connections. The tabs of the solenoid
coil are male tag terminals, and electrical connections
should be made using 1/4 in. (6.35 x 0.8 mm) female,
fully insulated push-on terminals. The earth ground
terminal is clearly labeled with the earth ground
symbol (see Figure 2).

Note: Electrical connections can also be made using
pre-wired electrical plugs (DIN 43650 [ISO 4400]).

Non-Polarity Sensitive
Connections

Ground Tab

25 VDC, 25V, 120V and 240V Only

1

L1 (Hot)

L2 (Neu)

1

Power supply provides disconnect
means and overload protection
as required.

Safety

Control

24 Volt

Thermostat

Limit(s)

Figure 2: Electrical Connections

X

indicates possible

locations for other controls.

Gas Flow

Shutoff Valve

BGA171/H96

Gas Valve

X

X

Sediment

Trap

3 in. (76.2 mm)

Minimum

Burner

Direction

of Flow

PRESS

TAP

OUT

IN

Figure 3: Typical BGA171/H96 Installation