Technical specifications – BASO G92 Series Automatic Pilot Gas Valve User Manual

Page 6

Advertising
background image

6 G92 Series BASOTROL Automatic Pilot Gas Valve Installation Instructions

Technical Specifications

Product

G92 Series BASOTROL Automatic Pilot Gas Valve

Maximum Operating

Pressure

0.5 psi (35 mbar)

Valve Body

Aluminum

Permissible Ambient

(Surface) Temperature

G92_ _ A and G92 _ _ C models without rotor valve

CSA:

-30 to 175ºF (-34 to 79ºC)

UL:

-30 to 125ºF (-34 to 52ºC)

G92_ _ B models with rotor valve

CSA:

32 to 175ºF (0 to 79ºC)

UL:

32 to 125ºF (0 to 52ºC)

Available Magnetic

Operator Cover Styles

Aluminum side conduit hub
Aluminum top conduit hub
Aluminum top without conduit hub
Aluminum side outlet with eyelet
Steel top conduit hub
Plastic with 1/4 in. (6.35 mm) male quick-connect terminals

Electrical Rating

25 VAC, 60 Hz, 0.3 ampere draw
120 VAC, 60 Hz, 0.05 ampere draw
240 VAC, 60 Hz, 0.03 ampere draw
208/240 VAC, 60 Hz, 0.037 ampere draw (UL only)
12 VDC, 0.5 ampere draw (CSA only)

Recommended

Thermocouple Lead

Lengths

K15: 12 to 48 in. (305 to 1,220 mm)
K16: 12 to 72 in. (305 to 1,830 mm)
K19: 18 to 72 in. (457 to 1,830 mm)

Wiring Connections

1/4 in. (6.35 mm) male quick-connect terminals or
30 in. (762 mm) lead wires (other lengths are optional)

Inlet Body Connection

1/2 in. NPT

Outlet Body Connection

1/2 or 3/4 in. NPT

Types of Gas

Natural, Liquefied Petroleum (LP), and LP gas-air mixtures

Packaging

Bulk pack supplied to original equipment manufacturer (individual pack optional)

Bulk Pack Quantity

32

Bulk Pack Weight

48 lb (22 kg)

Agency Listing

CSA Certificate Number 229521-1656050 (exclude G92CS_)
UL File Number MH2926 (excludes G92CV_ and G92D_ _)

Specification Standards

ANSI Z21.78, CSA 6.20
UL Standard 372 and 429

Performance specifications are nominal and conform to acceptable industry standards. All agency certification of BASO products is performed
under dry and controlled indoor environmental conditions. Use of BASO products beyond these conditions is not recommended and may void
the warranty. Product must be protected if exposed to water (dripping, spraying, rain, etc.) or other harsh environments. The original
equipment manufacturer or end user is responsible for the correct application of BASO products. Consult BASO Gas Products LLC for
questionable applications. BASO Gas Products LLC shall not be liable for damages or product malfunctions resulting from misapplication or
misuse of its products.

Refer to the G92 Series BASOTROL Automatic Pilot Gas Valve Product Bulletin (BASO-PB-G92) for necessary information on operating and
performance specifications of this product.

1007 South 12th Street
PO Box 170
Watertown, WI 53094

www.baso.com

1-877-227-6427 (1-877-BASOGAS)

Published in U.S.A.