2 H43 Series BASO Automatic Pilot Valve with Manual Shutoff Installation Instructions

5.

Attach the thermocouple securely to the pilot
burner, and screw the terminal end to the BASO®
power unit terminal on the valve. Make sure this
connection is clean. Tighten the thermocouple
lead nut finger tight, plus a maximum of 1/8 turn.
Do not overtighten.

6.

Attach the pilot gas line to the pilot burner fitting
and the pilot gas connection of the H43 valve.

!

WARNING: Risk of Explosion or Fire.

Verify that there are no gas leaks by testing with
appropriate equipment. Never use a match or lighter
to test for the presence of gas. Failure to test
properly can lead to an explosion or fire and may
result in severe personal injury or death.

7.

Check for leakage:

a. Shut off the gas at the main manual shutoff

valve and open the pressure connection
between the manual shutoff valve and the H43
valve.

b. Connect air tubing with a maximum pressure

of 1-1/2 times the valve’s maximum operating
pressure (as indicated on the valve) to the
opened pressure connection.

c. Paint all valve body connections with a rich

soap and water solution.

If bubbles occur, this is an indication of a leak.
To stop a leak, tighten joints and connections.
Replace the part if the leak cannot be stopped.

If bubbles do not occur, remove the air tubing
and close the pressure connection.

8. Perform

the

Checkout section before leaving the

installation.

Shutoff Valve

3 in. (76.2 mm)

Sediment Trap

Thermocouple

Lead

Pilot Burner

Gas Line

X

X

Reset Button

Handle and

Lock Pin Assembly

X indicates possible

locations for other controls.

fi

g1

Figure 1: Typical H43 Installation