L61LL BASO Safety Shutoff Device Installation Instructions

R

C

US

ELECTRICAL RATING:
CIRCUIT 1-2
8A. AT 120 V.A.C.
4A. AT 240 V.A.C.
1/4HP,
120/240 V.A.C.
CIRCUIT 1-3
125VA PILOT DUTY
120/240 VOLTS AC

L61LL-1

CIRCUIT #1-#2 #1-#3
PILOT ON CLOSED OPEN
PILOT OFF OPEN CLOSED

1

2

3

Do not loosen brass hex nut.
Must be tight to maintain continuity.

Figure 1: L61LL Product Label

6.

Replace the metal snap-on cover (do not loosen

the brass hex nut).

7.

Attach the thermocouple securely to the pilot
burner, and screw the terminal end to the BASO®
power unit terminal on the L61LL. Make sure that
this connection is clean. Tighten the thermocouple
lead nut finger tight plus 1/8 turn maximum. Do
not overtighten
.

Power Source

Transformer

Thermostat

X

X

L61LL

Safety Shutoff Device

Pilot

Valve

( Valve)

B

Basotrol

Valve

Thermocouple

Lead

Pilot Burner

Gas Line

X indicates possible

locations for other controls.

76.2 mm (3 in.)

Sediment

Trap

Main Manual

Shutoff Valve

( Valve)

A

BASO

Power Unit

Terminal

Figure 2: Typical L61LL Installation