Installation instructions (cont’d) – Kenmore POWER MISER 153.336851 User Manual
Page 10
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
1. When difcctly communicating with the outdoors, each open-
itie shall have a minimum free area of 1 square inch per 4,000
BTU per hour of total input rating of all equipment in the
enclosure. (See Figure 3.)
2.
When communicating with the outdoors through vertical
ducts, each opening shall have a minimum free area of 1
square inch per 4,000 BTU per hour of total input rating of
all equipment in the enclosure. (See Figure 4.)
Combustion Air and Ventilation
for Appliances Located in
Unconfined Spaces
Unoonfined Space
is a space whose volume is not less than 30
cubic feet per 1,000 Btu per hour of the aggregate input rating
of all appliances installed in that space. Rooms communicating
directly with the space in which the appliances are installed,
through openings not furnished with doors, are considered a
f
)art of the unconfincd space
n unconñned spaces in buildings, infiltration may be adequate
to provide air for combustion, ventilation and dilution or flue
gases. However, in buildings of tight construction (for example,
weather stripping, heavily insulated, caulked, vapor barrier, etc,),
additional air may need to be provided using the methods
described in Combustion Air and Ventilation for Appliances
Located in Confined Spaces, b.
Combustion Air and Ventilation
for Appliances Located in
Confined Spaces ,
Confined Space is a space whose volume is less than 30 cubic
feet per 1,000 Btu per hour of the agrégate input rating of all
appliances installed in that space,
a. ALL AIR FROM INSIDE BUILDINGS:
(See Page 8 Figure 1, and Figure 2 below)
The confined space shall be provided with two permanent
o^ni^
communicating
directly
with
an
additional
room(s)
of sufficient volume so that the combined volume of all
spaces meets the criteria for an unconñned space. The total
input of all gas utilization equipment installed in the com
bined space shall be considered in making this determination.
Each opening shall have a minimum free area of one square
inch per 1,000 BTU per hour of the total input rating of all
gas utilization equipment in the confined space, but not less
than 100 square inches. One opening shall commence within
12 inches of the top and one commencing within 12 inches
of the bottom of the enclosure.
Installation Instructions (cont’d)
Figure 4
3. When communicating with the outdoors through horizontal
ducts, each opening shall have a minimum free area of 1
square inch per 2,000 BTU per hour of total input rating of
all equipment in the enclosure. (See Figure 5.)
CHIMNEY ОЯ GAS VENT
Figure
2
Figure 5
01ЛЪЕТ AIR DUCT
INLET AIR DUCT
b. ALL AIR FROM OUTDOORS:
(see Figures 3-3)
The confined space shall be provided with two permanent
openings, one commencing within 12 inches of the top and
one commencing within 12 inches from the bottom of the
enclosure. The openings shall communicate directly, or by
ducts, with the outdoors or spaces (crawl or attic) that freely
communicate with the outdoors.
CHNNEY OG GAS VENT
,.VENTHAT)ON LOUVERS
hanIglalKI
Figure 3
WATER HEATER
•FURNACE
MLET AIR DUCT
ALT.MLETAJn VENTILATIQN LQUVSRS
4. When ducts arc used, they shall be of the same cross-sectional
area as the free area of the openings to which they connect.
The minimum short side dimension of rectangular air ducts
shall not be less than 3 inches. (Sec Figure 5.)
3. Louvers and Grilles: In calculating free area, consideration
shall be given to the blocking effect of louvers, grilles or
screens protecting opening. Screens used shall not be smaller
than
Yi
inch mesh. If the free area through a design of louver
or grille is known, it should be used in calculating the size
opening required to provide the free area specified. If the
design and free area is not known, it may be assumed that
wood louvers will be 20-25 percent free area and metal louvers
and grilles will have 60-75 percent free area. Louvers and
grilles shall be fixed in the open position or interlocked vnth
the equipment so that they are opened automatically during
equipment operation.
6. Special Conditions Created by Mechanical Exhausting or
Fireplaces: Operation of exhaust fans, ventilation systems,
clothes dryers or fireplaces may create conditions requiring
special attention to avoid unsatisiactory operation of installed
gas utilization equipment.
10